Error
Code

Name Description

60

Invalid analog output
poll command function

This analog output poll command contains an invalid function
code.

61

Invalid analog output
poll command

This analog output poll command is not valid.

70

Invalid time/date poll
command

This time/date object poll command is not valid.

80

Invalid event poll
command

This event poll command is not valid.

Application Layer Errors

Error
Code

Name Description

1000

Device index invalid

The device index in the request or response message is not
found in the slave list.

1001

Duplicate request in
application layer queue

The newly submitted message to the application layer
already exists in the queue. The message is ignored.

1002

COM port device
removed from system

The communication port for the message has been
uninstalled on the system. This error should never occur as
the communication ports are only uninstalled when the
module's program is terminated.

1003

Sequence number error The application sequence number in the response message

does not match that based on the last request message. This
indicates application layer messages are received out of
order.

1004

Response to select
before operate does not
match

The select response message received from the slave
module is not that expected from the last select request. This
indicates a synchronization problem between the master and
slave devices.

1005

Response does not
contain date/time object

The response message from the slave device does not
contain a date/time object. The master expects this object for
the response message.

1006

Time-out condition on
response

The slave device did not respond to the last request
message from the master within the time-out set for the IED
device. The application layer time-out value is specified for
each IED unit in the slave configuration table in the module.
This table is established each time the module performs the
restart operation.

1007

Function code in
application layer
message not supported

The function code returned in the response message is not
valid for the application layer or not supported by the module.

1008

Read operation not
supported for
object/variation

The application layer response message contains an object
that does not support the read function.

1009

Operate function not
supported for the
object/variation

The application layer response message contains an object
that does not support the operate function.

1010

Write operation not
supported for the
object/variation

The application layer response message contains an object
that does not support the write function.