[Section]/Item Value

Range

Description

PLC Counters:

0 to 240 points Number of counter points configured above that are to

be obtained from the CompactLogix processor. All
other counter points must come from the attached IED

units.

Binary Outputs:

0 to 7680
points

Number of digital output points to configure in the DNP
slave device. Each point will be stored as a single bit in

the module memory.

PLC Binary Outputs:

0 to 7680
points

Number of digital output points configured above that
are to be sent to the CompactLogix processor. All
other binary output points will be sent to the attached

IED units.

Analog Outputs:

0 to 480 points Number of analog output points to configure in the

DNP slave device. Each point will occupy a one word

area in the module memory.

PLC Analog Outputs:

0 to 480 points Number of analog output points configured above that

are to be sent to the CompactLogix processor. All
other analog output points will be sent to the attached
IED units.

Float Outputs:

0 to 240 points Number of floating-point output points to configure in

the DNP slave device. Each point will occupy a two-
word area in the module memory.

PLC Float Outputs:

0 to 240 points Number of floating-point output points configured

above that are to be sent to the CompactLogix.


[Section]/Item

Description

[DNP Slave Binary Inputs]

DNP database binary input override values

# This area is to override the class assignment for binary input database points. Enter list of points between the
# START and END labels.

#

# Point# Class

START

END


[Section]/Item

Description

[DNP Slave Analog Inputs]

DNP database analog input override values

START

# This area is to override the class and deadband assignment for analog input database points.
# Enter list of points between the START and END labels.
#
# Point# Class Deadband
START

END


[Section]/Item

Description

[DNP Slave Float Inputs]

DNP database floating-point input override values

# This area is to override the class and deadband assignment for float input database points.
# Enter list of points between the START and END labels.
#
# Point# Class Deadband

Advertising