ProSoft Technology MVI69-DNP User Manual

Page 116

Advertising
background image

MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 116 of 129

ProSoft Technology, Inc.

November 3, 2008

OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

3

32-Bit Frozen Analog
Event With Time

88

4

16-Bit Frozen Analog
Event With Time

72

40 0 Analog

Output

Status: All Variations

1

06

24

1

32-Bit Analog Output
Status

40

2

16-Bit Analog Output
Status

129, 130 00, 01

24

Master does not use this
object type and will not
generate a message or
process this type

41

0

Analog Output Block:
All Variations

24

1

32-Bit Analog Output
Block

40

2

16-Bit Analog Output
Block

3, 4, 5, 6 17, 28

129

Echo of
Request

24

Master will generate this
variation and parse the
response

50

0

Time and Date: All
Variations

48

1

Time and Date

2

07, With
Quant=1

48

Master will generate this
variation

2

Time and Date With
Interval

80

51

0

Time and Date CTO:
All Variations

1

Time and Date CTO

129, 130 07, With

Quant=1

48

Master will process this
variation

2

Unsynchronized
Time and Date CTO

129, 130 07, With

Quant=1

48

Master will process this
variation

52

0

Time Delay: All
Variations

1

Time Delay Coarse

129

07, With
Quant=1

16

Master will not process
this variation

2

Time Delay Fine

129

07, With
Quant=1

16

Master will not process
this variation

60

0

Not Defined

Not Defined in DNP

1

Class 0 Data

1

06

Master will generate this
variation

2

Class 1 Data

1

06, 07, 08

Master will generate this
variation

3

Class 2 Data

1

06, 07, 08

Master will generate this
variation

4

Class 3 Data

1

06, 07, 08

Master will generate this
variation

70

0

Not Defined

Advertising