ProSoft Technology MVI69-DNP User Manual

Page 43

Advertising
background image

Ladder Logic

MVI69-DNP ♦ CompactLogix or MicroLogix Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 43 of 129

November 3, 2008

Tag Name

Data Type

Description

Blk_WErr

Decimal

Total number of write block errors

Blk_NErr

Decimal

Total number of block number errors

Blk_ECntr

Decimal

Number of sequential block errors

Blk_EFlag

Decimal

Block error flag

Cfg_Type

Decimal

0=Single Slave, 1-Dual-Slave, 2=Slave/Master

Product Decimal

Product

name

Rev Decimal

Revision

Op_Sys

Decimal

Operating system revision

Run Decimal

Run

number

Slave_Count

Decimal

Number of slaves configured

Cmd_Count

Decimal

Number of commands configured

Mem_Blk Decimal

Number

of memory blocks allocated

Mem_Frame Decimal

Number

of frame blocks allocated

Mem_DLRec Decimal

Number

of

receive DL blocks allocated

Mem_DLTx Decimal

Number

of

transmit DL blocks allocated

Mem_AppRec

Decimal

Number of receive app blocks allocated

Mem_AppTx

Decimal

Number of transmit app blocks allocated

Mem_DevErr Decimal

Number

of device mem alloc errors

Mem_PhyErr

Decimal

Number of physical layer mem alloc errors

Mem_DLRErr

Decimal

Number of data-link layer receive mem alloc errors

Mem_DLTErr

Decimal

Number of data-link layer transmit mem alloc errors

Mem_AppRErr

Decimal

Number of app layer receive mem alloc errors

Mem_AppTErr

Decimal

Number of app layer transmit mem alloc errors

Mstr_Sync

Decimal

Number of master port synchronization errors

Mstr_Length

Decimal

Number of master port length errors

Mstr_CRC

Decimal

Number of master port CRC errors

Scan_Count

Decimal

Program scan counter

Mem_Free

Decimal

Free memory for module

P1_TX_State Decimal

State

of

Port 1 transmit state machine

FloatEvents

Decimal

Count of floating-point events

DoubleEvents

Decimal

Count of double floating-point events

EventQueue Decimal

Total number of events in message queue for
processor

EvtQueueOF

Decimal

Event message queue overflow flag (0=no, 1=yes)

Ladder logic is required to transfer the data sent from the module to the
processor into this data object. If the ladder logic is present and the module is
operating, this object can be viewed in the Controller Tags Monitor window to
observer the current status of the module.

Advertising