OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

2

16-Bit Counter
Change Event
Without Time

129, 130 17, 28

24

Master will process this
variation

3

32-Bit Delta Counter
Change Event
Without Time

40

4

16-Bit Delta Counter
Change Event
Without Time

24

5

32-Bit Counter
Change Event With
Time

88

6

16-Bit Counter
Change Event With
Time

72

7

32-Bit Delta Counter
Change Event With
Time

88

8

16-Bit Delta Counter
Change Event With
Time

72

23 0 Frozen

Counter

Event: All Variations

1

32-Bit Frozen
Counter Event
Without Time

40

2

16-Bit Frozen
Counter Event
Without Time

24

3

32-Bit Frozen Delta
Counter Event
Without Time

40

4

16-Bit Frozen Delta
Counter Event
Without Time

24

5

32-Bit Frozen
Counter Event With
Time

88

6

16-Bit Frozen
Counter Event With
Time

72

7

32-Bit Frozen Delta
Counter Event With
Time

88

8

16-Bit Frozen Delta
Counter Event With
Time

72

30

0

Analog Input: All
Variations

1

06

16

Master will generate this