Diagnostics and Troubleshooting

MVI69-DNP ♦ CompactLogix or MicroLogix Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 67 of 129

November 3, 2008

Bit Description

Value

11

0x0800

12

0x1000

13

0x2000

14

0x4000

15

0x8000

Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
word will be clear. This does not indicate that the configuration is valid for the
user application. Make sure each parameter is set correctly for the specific
application.

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.

4.2.1 Clearing a Fault Condition

Typically, if the OK LED on the front of the module turns red for more than ten
seconds, a hardware problem has been detected in the module, or the program
has exited.

To clear the condition, follow these steps:

1 Turn off power to the rack
2 Remove the card from the rack
3 Verify that all jumpers are set correctly
4 If the module requires a Compact Flash card, verify that the card is installed

correctly

5 Re-insert the card in the rack and turn the power back on
6 Verify the configuration data being transferred to the module from the

CompactLogix or MicroLogix processor.

If the module's OK LED does not turn green, verify that the module is inserted
completely into the rack. If this does not cure the problem, contact ProSoft
Technology Support.