ProSoft Technology MVI69-DNP User Manual

Page 70

Advertising
background image

MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 70 of 129

ProSoft Technology, Inc.

November 3, 2008

5.1.2 Hardware

Specifications

Specification Description

Dimensions

Standard 1769 Single-slot module

Current Load

800 mA max@ 5 VDC

Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)

Operating Temp.

0 to 60°C (32 to 140°F)

Storage Temp.

-40 to 85°C (-40 to 185°F)

Relative Humidity

5% to 95% (non-condensing)

LED Indicators

Battery and Module Status

Application Status

Serial Port Activity

CFG Port Activity

CFG Port (CFG)

RJ45 (DB-9F with supplied cable)

RS-232 only

No hardware handshaking

App Ports (P1,P2) (Serial modules)

RS-232, RS-485 or RS-422 (jumper selectable)

RJ45 (DB-9F with supplied cable)

RS-232 handshaking configurable

500V Optical isolation from backplane

Shipped with Unit

RJ45 to DB-9M cables for each port

6-foot RS-232 configuration Cable

5.1.3 Functional

Specifications

The MVI69-DNP module supports the DNP 3.0 protocol with a minimum of Level
2 functionality. DNP protocol Subset Definitions for the Master and the Slave
drivers are available in the module's User Manual.

The module has two DNP protocol ports that can be user configured to operate in
a Master/Slave or in a Slave/Slave redundant port configuration.

User defined internal register space is accessible to the protocol driver and to the
CompactLogix processor memory.

Redundant Slave Port Operation

When configured in the Slave/Slave port configuration, the module's slave ports
operate in a primary and secondary fashion. In this mode, a single host polls the
module via redundant physical layer connections. Several methods are
supported to automatically switch between the primary and secondary slave
ports.