MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Configuring the MVI69-DNP Module

DNP 3.0 Master/Slave Communication Module

Page 24 of 129

ProSoft Technology, Inc.

November 3, 2008

[Section]/Item Value

Range

Description

CD Time Before Receive:

0 to 65535

Defines the number of milliseconds to wait before
receiving characters after the CD signal is recognized

as high.

BI Class:

0 to 3

This parameter specifies the default class to be utilized
for all the binary input points in the DNP database that

are not defined in the override list section.

AI Class:

0 to 3

This parameter specifies the default class to be utilized
for all the analog input points in the DNP database that

are not defined in the override list section.

Float Class:

0 to 3

This parameter specifies the default class to be utilized
for all the floating-point input points in the DNP
database that are not defined in the override list

section.

AI Deadband:

0 to 32767

This parameter specifies the default deadband value
assigned to all points not defined in the override list for

the analog input point type in the DNP database.

Float Deadband:

0 to maximum
float value

This parameter specifies the default deadband value
assigned to all points not defined in the override list for

the floating-point input point type in the DNP database.

Select/Operate Arm Time:

1 to 65535
milliseconds

Time period after select command received in which
operate command will be performed. After the select
command is received, the operate command will only
be honored if it arrives within this period of time.

Write Time Interval:

0 to 1440

minutes

Time interval to set the need time IIN bit (0=never),
which will cause the master to write the time. Stored in
milliseconds in the module memory.

Data Link Confirm Mode:

Coded Value
(N=Never,
S=Sometimes,

A=Always)

IED can request acknowledgement from master station
when sending data. The codes are as follows:
0=Never, 1=Sometimes, 2=Always

Data Link Confirm Tout:

1 to 65535
milliseconds

Time period to wait for Master Data Link confirmation
of last frame sent. This time is in milliseconds. This
parameter is only used if the frame is sent with

confirmation requested.

Data Link Max Retry:

0 to 255 retries Maximum number of retries at the Data Link level to

obtain a confirmation. If this value is set to 0, retries
are disabled at the data link level of the protocol. This
parameter is only used if the frame is sent with

confirmation requested.

App Layer Confirm Tout:

1 to 65535
milliseconds

Event data contained in the last response may be sent
again if not confirmed within the millisecond time
period set. If application layer confirms are used with
data link confirms, ensure that the application layer

confirm timeout is set long enough.

Unsolicited Response:

Yes or No

Set if the slave unit will send unsolicited response
messages. If set to No, the slave will not send
unsolicited responses. If set to Yes, the slave will send

unsolicited responses.

Class 1 Unsol Resp Min:

1 to 255 events Minimum number of events in Class 1 required before

an unsolicited response will be generated.

Class 2 Unsol Resp Min:

1 to 255 events Minimum number of events in Class 2 required before

an unsolicited response will be generated.

Class 3 Unsol Resp Min:

1 to 255 events Minimum number of events in Class 3 required before

an unsolicited response will be generated.