MVI69-DNP ♦ CompactLogix or MicroLogix Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 104 of 129

ProSoft Technology, Inc.

November 3, 2008

5.6

DNP V3.00 Device Profile Document

Vendor Name:

ProSoft Technology, Inc.

Device Name:

MVI69-DNP (Revision 1.00)

Highest DNP Level Supported:

Device Function:

For Request: L2
For Responses: L2

Slave & Master

Notable objects, functions, and/or qualifiers supported in addition to the highest DNP level stated above (see attached
table for complete list):
Definition of selected IIN bits: Configuration Error - User specified point or event count is too high for application (can only
correct by changing configuration in PLC).
Support for a redundant slave port on the module which may be attached to a dial-up modem is provided. Auto switching
is provided by the module to switch between the primary and secondary ports.
The following features are configurable on the module: Collision avoidance, time sync before events are generated and
default analog input events, Obj32V4 or O32V2, select option.
Events generated by IED units attached to a master port may pass their events directly to the slave port. These events
may not occur in the correct time sequence. They are placed in the event buffer as the module receives them. This
provides the greatest time resolution for remote events.
Module will not generate events until Restart IIN bit is cleared by DNP master except for events passed through module
from attached IED units.
Maximum Data Link Frame Size (octets):

Maximum Application Fragment Size (octets):

Transmitted: 292
Received: 292

Transmitted: 2048
Received: 2048

Maximum Data Link Re-tries:

Maximum Application Layer Retries:

Configurable from 0 - 255

None

Requires Data Link Layer Confirmation:

Configurable at module start-up (never, sometimes, & always)

Requires Application Layer Confirmation:

When reporting Event Data as a slave unit

Time-outs while waiting for:

Data Link Confirm

: Configurable at module start-up (1 to 65535 milliseconds)

Complete Application Fragment

: Configurable at module start-up

Application Confirm

: Configurable at module start-up (1 to 65535 milliseconds)

Complete Application Response

: None

Sends/Executes Control Operations:

WRITE Binary Outputs

: Never

SELECT/OPERATE :

Always

DIRECT OPERATE

: Always

DIRECT OPERATE-NO ACK

: Always


Count > 1

: Always (1 to 65535)

Pulse On

: Always

Pulse Off

: Always

Latch On

: Always

Latch Off

: Always