OBJECT

REQUEST

RESPONSE

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

NOTES

4

16-Bit Delta Counter

129, 130 00, 01

24

Master will process this
variation

5

32-Bit Binary
Counter Without Flag

1, 7, 8,
9, 10

06

129, 130 00, 01

32

Master will generate and
process this variation

6

16-Bit Binary
Counter Without Flag

1, 7, 8,
9, 10

06

129, 130 00, 01

16

Master will generate and
process this variation

7

32-Bit Delta Counter
Without Flag

129, 130 00, 01

32

Master will process this
variation

8

16-Bit Delta Counter
Without Flag

129, 130 00, 01

16

Master will process this
variation

21

0

Frozen Counter: All
Variations

1

06

32

Master will generate this
variation

1

32-Bit Frozen
Counter

129, 130 00, 01

40

Master will process this
variation

2

16-Bit Frozen
Counter

129, 130 00, 01

24

Master will process this
variation

3

32-Bit Frozen Delta
Counter

40

4

16-Bit Frozen Delta
Counter

24

5

32-Bit Frozen
Counter With Time
Of Freeze

88

6

16-Bit Frozen
Counter With Time
Of Freeze

72

7

32-Bit Frozen Delta
Counter With Time
Of Freeze

88

8

16-Bit Frozen Delta
Counter With Time
Of Freeze

72

9

32-Bit Frozen
Counter Without Flag

1

06

129, 130 00, 01

32

Master will generate and
process this variation

10

16-Bit Frozen
Counter Without Flag

1

06

129, 130 00, 01

16

Master will generate and
process this variation

11

32-Bit Frozen Delta
Counter Without Flag

32

12

16-Bit Frozen Delta
Counter Without Flag

16

22 0 Counter

Change

Event: All Variations

1

06, 07, 08

Master will not generate a
request for this variation

1

32-Bit Counter
Change Event
Without Time

129, 130 17, 28

40

Master will process this
variation

Advertising