2-118

Remote Control Functions

6. Communication Adaptor (SHA-KA128AAB)

[1] Adaptor number setting

xx = 00 to 15: adaptor number

Sets the Communication Adaptor number.

Set 1 to 7 for the Intelligent Controller, making sure the same number is not used twice.

When actually communicating from a master system, the link system address LINK1 is 2n and
LINK2 is 2n + 1, where n is the Communication Adaptor number.
Thus, when the adaptor number is 2, the LINK1 address is 4 and the LINK2 address is 5.

[7] Local Adaptor connection settings

x = 0: LINK 1 on, LINK2 on

x = 1: LINK 1 off, LINK2 on

x = 2: LINK 1 on, LINK2 off

x = 3: LINK 1 off, LINK2 off

Set whether there is a Local Adaptor (for turning off and on) for each LINK system. If the setting
is “off”, startup will be faster as no Local Adaptor detection is run.

Table 1 Communication Adaptor setting items

Display

[2] Indoor/outdoor control wire connection settings

x = 0: LINK1 on, LINK2 on

x = 1: LINK1 on, LINK2 off

x = 2: LINK1 off, LINK2 on

x = 3: LINK1 off, LINK2 off

Set so any LINK (indoor/outdoor control wire) connected to the air conditioner is “on”, and any LINK
not connected is “off”.

* For solo installation (pulse meter dedicated), use x = 3: LINK1 and 2 both set to off.

(1.Ano.xx)

[3] Base unit settings

Always use 0 (the initial value).

(2.AdYu.x)

(3.Cont.x)

(4.CAn1.x)

(5.CAn2.x)

(6.PUL.xx)

(7.LoCA.x)

(8.SCAn.x)

[4] Settings for the number of Communication Adaptor units in one link, part 1

x = 0 to 7

x = 0: First Communication Adaptor in the LINK1 link

x = 1: Second Communication Adaptor in the LINK1 link

x = 7: Eighth Communication Adaptor in the LINK1 link

[5] Settings for the number of Communication Adaptor units in one link, part 2

x = 0 to 7

x = 0: First Communication Adaptor in the LINK2 link

x = 1: Second Communication Adaptor in the LINK2 link

x = 7: Eighth Communication Adaptor in the LINK2 link

Set the Communication Adaptor unit number for each LINK system when connecting multiple
Communication Adaptors to one indoor/outdoor control wire.

[6] Minimum pulse input detection time setting

x = 03: 30 msec

x = 10: 100 msec

If connecting a pulse meter with a pulse width between 30 and 100 msec, set to 30 msec.

[8] Initial communication setting

Always use 0 (the initial value).

Setting item ( grayed in areas indicate factory setting)

DOWN

UP

Connecting to external equipment

5

(1) External all input (No-voltage a-contact

static)

DI–COMMON

DI 1

DI 2

DI 3

(2) External all output (No-voltage a-contact

static)

DO–COMMON

DO 1

DO 2

(3) Pulse meter input (No-voltage a-contact

pulse)

P–COMMON

P1

P2

P3

Minimum pulse width: 100 msec

Minimum pulse interval: 1 sec

(

*

) Input/output function when connecting to the Intelligent

Controller

Gas flow meter (

*

)

(fuel flow meter)

Keep the signal input line lengths to 66 ft. or less. For distances greater than this, install a standalone Communication Adaptor or use
a relay.

For use in areas that may be susceptible to electrical noise, use a two-conductor shielded cable (with one line grounded), with a cross-
section at least AWG#20.

Do not apply external voltages to the input terminals.

About 10 mA of 5 V DC voltage is applied to the contact point for input terminal detection.

The output terminal allowable contact voltage and current are 30 V DC and 0.5 A.

All stop input (

*

)

All operation input (

*

)

(Reserved)

(Common output)

(

*

) All alarm output

(

*

) All operation output

Equipment

t

u

p

ni

l

ati

gi

D

Power flow meter 1 (

*

)

Power flow meter 2 (

*

)

Outer dimensions

6

Specifications

Rated voltage ........................................ Single phase 100 to 240V
Rated frequency ................................... 50/60 Hz
Power consumption .............................. 5.6 W max
Operating temperature ......................... 14–122ºF (–10 to +50ºC)
Operating humidity ............................... 20 to 80% (no condensation)
Weight ................................................... 3.97lb (1.8 kg)

7

Equipment

1

0

-5

/6

4

11-27/64

3

-7

/6

4

1

-1

/2

3- 7/8

(in.)

1

-1

/2

13/64

7

-3

/3

2

10-5/8

25/64