Timer remote controller (rcs-tm80bg) – Sanyo CHX06052 User Manual

Page 47

Advertising
background image

2-29

Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

2

1. press and hold

for more than 2 seconds to display the upper limit temperature

setting screen.

,

and the upper limit temperature start flashing.

(The default value of the upper limit temperature is 99 °F (37°C).)

2. press

/

to select the upper limit temperature and press

to fix the

value. The lower limit temperature setting screen is displayed.

3. press

/

to select the lower limit temperature, and press

to fix the

value. The outing function setting is completed. (The default value of the lower limit
temperature is 50 °F (10°C).)

*

The unit returns to the normal mode if

is pressed or there is no operation made for 3

minutes during the setting. In this case, all the settings in progress will be lost.

Canceling the outing function

Press and hold

for more than 2 seconds while the outing function is set.

Setting the Outing Function

Outing function indication

Outing function indication

Status

Off

The outing function is not set.

Flashing

The outing function is now being set, or under operation.

Lighting

Although the outing function is set, not under operation.

Note

A remote controller loses outing function operation information when it is cut for more than one hour during the outing function
operation by electricity. It reverts from the blackout, and an air conditioner does not drive in outing function when operation is
started. At this time, an air conditioner does not stop at outing function.

2

Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no
one is in the room.
An air conditioner works automatically if this function is set effective.

COOL / DRY

Room temperature

Room temperature

For Example

Setting at Outing Temperature 86°F(30

͠

Outing function Upper limit

HEAT

Outing function Lower limit

General Performance of the Outing Function

The air conditioner starts operation when the room temperature decreases up to +1.8°F(1

͠

) of the lower limit.

The air conditioner stops operation when the room temperature increases up to +3.6°F(2

͠

) of the lower limit.

The air conditioner starts operation when the room temperature increases up to –1.8°F(1

͠

) of the upper limit.

The air conditioner stops operation when the room temperature decreases up to –3.6°F(2

͠

) of the upper limit.

[Precautions]

The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting.

Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air condition-
er with your desired operation mode/ temperature setting.

If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing func-

tion is activated.

The outing function is invalid during FAN/AUTO operation mode.
The air conditioner's stop order (stated in /above) is valid only when the outing function is operated.

If operated using other remote control unit (or a centralized control device such as a system control), the outing function does
not work.

(ON)

(ON)

(OFF)

(OFF)

3.6°F(2

͠

3.6°F(2

͠

1.8°F(1

͠

1.8°F(1

͠

86°F

30

͠

84°F(29

͠

82°F(28

͠

57

(

14

͠

55 F(13

͠

53 F(12

͠

For Example

Setting at Outing Temperature 53°F(12

͠

(Setting at Outing Temperature)

(Setting at Outing Temperature)

3

MiniECO-i.indb 29

2007/06/20 16:28:45