Timer remote controller (rcs-tm80bg) – Sanyo CHX06052 User Manual

Page 54

Advertising
background image

2-36

Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

Item code

Item

No.

Description

No.

D

Setting data

escription

No.

Description

0000

1-Way Air Discharge

0001

4-Way Air Discharge

Semi-Concealed

0005

0008

0006

0007

Type

Indoor unit

capacity

0001

Unit No. 1 (Outdoor unit system (outdoor unit) address is “1”.)

0002

Unit No. 2 (Outdoor unit system (outdoor unit) address is “2”.)

0003

Unit No. 3 (Outdoor unit system (outdoor unit) address is “3”.)

0030

Unit No. 30 (A setting which exceeds this number of units is not possible.)

(A setting which exceeds this number of units is not possible.)

System

address

0099

(In this case, the system (outdoor unit) address must be set.)

System (outdoor unit) address is undefined.

0001

Unit No. 1

0002

Unit No. 2

0003

Unit No. 3

0064

Unit No. 64

Indoor unit

address

0099

Indoor unit address is undefined. (In this case, the indoor unit address must be set.)

0000

Individual (indoor units where group control wiring has not been connected)

Main unit (one of the indoor units where group control is in effect)

Sub units (all indoor units other than the main unit where group control is in effect)

0001

0002

Group

address

Semi-Concealed

No.

Description

Concealed-Duct

Wall-mounted

Concealed-Duct High

Static Pressure

Ceiling-Mounted

(Outdoor unit)

2

0

0

0

1

0

0

0

0

0

0

0

5

0

0

0

4

0

0

0

3

0

0

0

8

0

0

0

7

0

0

0

6

0

0

0

1

1

0

0

0

1

0

0

9

0

0

0

4

1

0

0

3

1

0

0

2

1

0

0

7

1

0

0

6

1

0

0

5

1

0

0

1

2

0

0

0

2

0

0

8

1

0

0

0023

5

2

2

2

d

e

l

b

a

s

i

d

6

3

2

3

8

2

0

5

5

4

0

4

1

7

3

6

6

5

0

0

1

0

9

0

8

0

4

1

5

2

1

2

1

1

160

280

4

2

2

0

0

2

T10

terminal

switching

0000

0001

0002

Used for OFF reminder

HA terminal (At time of shipment)

Fire prevention input

0000

0001

0000

Switching to

the remote

controller

sensor

0001

Operation not permitted. (Setting at time of shipment)

Operation permitted.

Operation

of the

ventilation fan

from the

remote

controller

Body sensor (setting at time of shipment)

Remote controller sensor

List of Detailed Setting Items

Filter sign ON time setting
(filter lifetime)

Changes the indoor unit filter lifetime when a high-performance filter or
other optional product is installed.

01

Item

code

n

o

i

t

p

i

r

c

s

e

D

m

e

t

I

g

g

g

g

h

Model

data

Model

Filter sign ON times for each model

Standard

High

performance

65

High

performance

90

Long-life

Super long-life

Filter sign ON time

Pressure

differential

switch

Standard

High

fouling

Standard

High

fouling

Standard

High

fouling

Standard

High

fouling

Standard

High

fouling

0000

75

150

150

75

2500

1250

5000 2500 2500 1250

2500 1250

5000

2500

2500

1250

5000

2500

2500 1250

2500

1250

5000

2500

2500

1250

2500

1250

0001

0005

0006

0007

0008

1-Way Air Discharge
Semi-Concealed

4-Way Air Discharge
Semi-Concealed

Concealed Duct

Concealed Duct
High Static Pressure

Ceiling-Mounted

Wall-Mounted

NOTE

indicates that there is no corresponding filter.

indicates the filter sign ON time that is set at the time of shipment.

List of Simple Setting Items

MiniECO-i.indb 36

2007/06/20 16:28:51