2-51

Remote Control Functions

4. System Controller (SHA-KC64UG)

2

2. Address switch setting

How to reach the P.C. board
Remove the cross flat head screw on the bottom of the back case. When
you open up the decorative cover, you will see two notches under the
control unit. Inset a coin or other flat object into these notches and pry off
the back case. The P.C. board on the back of the control unit is now visible.

WARNING

To avoid an electric shock hazard,

DO NOT touch any terminal on the

Printed Circuit Board with a metal

rod, a screwdriver edge nor a bare

hand when power is supplied.

After installation and adjust-

ment, be sure to turn the

BACK UP switch ON.

All bits are set off

when shipped from

factory.

To Installers,

PCB of the control unit

Gap

Coin

Gap

2 - 51

SW1

1

ON

ALL mode
ZONE 1 mode
ZONE 2 mode
ZONE 3 mode
ZONE 4 mode

OFF
OFF

ON

OFF

ON

2

OFF
OFF
OFF

ON
ON

3

OFF

4

OFF

ON
ON
ON
ON

5

OFF

2 3 4

SW1

5 6 7 8

Main/sub selection switch

OFF: System controller operates as main controller.

ON: System controller operates as sub-controller.

ALL/ZONE mode selection switch

ALL mode:

All indoor units can be controlled by system controller ZONE

1, 2, 3, 4 mode:

Indoor units in one of zone 1, 2, 3, or 4 can be controlled by

system controller. All indoor units cannot be set.

Central control/Remote control mode selection switch

OFF: Central control mode.

Individual setting by remote controller can be inhibited by

system controller.

ON: Remote control mode.

Setting by system controller is inhibited by other central

control equipments.

Central control Main/Sub selection switch

(OFF: Main, ON: Sub)

When AMY adaptor etc. is used with system controller,

set the switch to ON position.

When only one system controller is used, set the switch

to OFF position.

Except , when multiple system controllers are used, set

only one system controller to OFF position and others to

ON position.

ALL mode system controller should be in OFF position.

(recommended)

1

2

3

1

(Central control) button operation switch

OFF:

(Central control) button operation is permitted.

ON :

button operation is inhibited.

*All switches are OFF position at shipment.