Lonworks interface product manual (sha-ln16uab), Details of lonworks network variables – Sanyo CHX06052 User Manual

Page 150

Advertising
background image

2-132

Remote Control Functions

7. LonWorks Interface product Manual (SHA-LN16UAB)

7. Details of LonWorks Network Variables

[nv1] Unit start/stop command

network input SNVT_switch nviOnOff_0 0;

network input SNVT_switch nviOnOff_0 1;

network input SNVT_switch nviOnOff_0 2;

network input SNVT_switch nviOnOff_0 3;

These input n etwork v ariables ar e used to ch ange the start/stop

status of the ind oor unit.

If star t/stop is only done from an A/ C unit side (as with the rem o te

controll er), th en it is not n e c e ssary to use th ese n e twork vari ables .

Contents

state 0: Stop

value (Not used)

1: start

[nv2] Unit start/stop status notification

network output SNVT_sw itch nvoOnOff_0 0 ;

network output SNVT_sw itch nvoOnOff_0 1 ;

network output SNVT_sw itch nvoOnOff_0 2 ;

network output SNVT_sw itch nvoOnOff_0 3 ;

These output n e twork v a riab les ar e us ed to pro v ide notification of

the un it’s cur r en t s t ar t/s top s t atus and the therm o s t at ON/OF F s t atus .

The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C

unit side (as wit h the rem o te con t roller) .

They are outp ut when the Lo nWorks Interface or the A/C u nit

power is r e set.

When the ind oor units ar e su bject to group control, “thermostat

ON” is output when 1 or more indoor unit is thermostats ON, and

“thermostat OFF” is ou tput w hen all indoor unit are thermo stats

OFF.

Contents

state 0: Stop value 0: T hermostat OF F

1: Start

200: T hermostat ON

[nv3] Te mperature setting command

network input SNVT_temp _p nviS etpoin t _0 0;

network input SNVT_temp _p nviS etpoin t _0 1;

network input SNVT_temp _p nviS etpoin t _0 2;

network input SNVT_temp _p nviS etpoin t _0 3;

These inpu t n e twork variables ar e used to change the indoor unit

tem p eratur e s e tti ng.

If th e tem p era t ure se tting is onl y ch anged from an A/C uni t sid e (as

with the r e m o te control l er) , the n it is not n e c e ssar y to use th ese

network var iables.

When a temper ature above th e u pper limit of the temper ature wh ich

can be set b y the indoor units has been specified, it will be set to the

upper limit; con versely, when a temperatur e b elow the low er limit

has been spec ifi e d, it will be set to th e lower l i m it.

Contents

Valid ra ng e

Auto heat/cool mode: 62 - 80°F (17 - 27°C)
Heat mo de:

60 - 78°F (16 - 26°C)

Cool mo de:

64 - 86°F (18 - 30°C)

Dr y mo d e :

64 - 86°F (18 - 30°C)

F an mode:

Temp. setting not used.

Temperature settings are made in units of 1.8°F (1.0°C). (Values

°

after the decimal point are discarded.)

* Be awa r e tha t t h e tem p eratur e setting r a nges m a y var y a ccord ing to

the models of th e outdoor and in door units.

[nv4] T emperature setting status notification

network output SNVT_temp_p nvoSetpo int_01;

network output SNVT_temp_p nvoSetpo int_01;

network output SNVT_temp_p nvoSetpo int_02;

network output SNVT_temp_p nvoSetpo int_03;

These output network v ariables ar e output w h en the temperature

setting status is changed.

The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C

unit side (with th e rem o te con t rol l er).

They are outp ut when the Lo nWorks Interface or the A/C u nit

power is r e set.

Contents

Valid ra ng e

Output range:

60-86°F (16-30°C)

T e m p . u n i t :

1.8°F (1.0°C)

* Be awa r e tha t t h e tem p eratur e setting r a nges m a y var y a ccord ing to

the models of th e outdoor and in door units.

[nv5] Operating mode setting command

network input SNVT_hva c _mode nviHea tC ool_00;

network input SNVT_hva c _mode nviHea tC ool_01;

network input SNVT_hva c _mode nviHea tC ool_02;

network input SNVT_hva c _mode nviHea tC ool_03;

These input n etwork v ariables ar e used to change the indoor u nit

operating mode.

If the op erating mode setting is on ly changed from an A/C unit

side (as with th e rem o te control l er), then it is n o t nec e ssar y to use

thes e n e twork v a riables .

Contents

0: Auto heat/cool

5: Dry

1: Heat

9: F a n

3: Cool

* Th e operating modes that can be set may va ry ac c o rding t o the

models of the ou tdoor and indoor units.

* Settings other than th e above ar e ignor ed.

[nv6] Operating mode status notification

network output SNVT_hvac_mode nvoH eatCool_00;

network output SNVT_hvac_mode nvoH eatCool_01;

network output SNVT_hvac_mode nvoH eatCool_02;

network output SNVT_hvac_mode nvoH eatCool_03;

These output n e twork v a riab les ar e ou tput wh en the operating m ode

has been ch anged.

The y are als o o u tput when th e s t atus h a s be en ch anged from an A / C

unit side (with th e rem o te con t rol l er).

They are outp ut when the Lo nWorks Interface or the A/C u nit

power is r e set.

Contents

0: Auto heat/cool 5: Dr y

1: Heat

9: F a n

3: Cool

[nv7] Option 1 setting command
[nv9] Option 2 setting command

network input SNVT_switch nviOption1_0 0;

network input SNVT_switch nviOption1_0 1;

network input SNVT_switch nviOption1_0 2;

network input SNVT_switch nviOption1_0 3;

network input SNVT_switch nviOption2_0 0;

network input SNVT_switch nviOption2_0 1;

network input SNVT_switch nviOption2_0 2;

network input SNVT_switch nviOption2_0 3;

These inpu t n e twork variables are used to make th e indoor unit

option settings.

Two of the following 4 option settings can be selected:

remote-contro ller prohibit, fan speed setting, air di rection setting,

and filter sign r e set.

Make ch anges using the DIP switc hes on the main circuit bo ard.

When option s ettings are not made from the LonWorks, it is not

neces s a r y to us e thes e n e twork v a riables .

[nv8] Option 1 setting status notification
[nv10] Option 2 setting status notification

network output SNVT_sw itch nvoOption1 _00;

network output SNVT_sw itch nvoOption1 _01;

network output SNVT_sw itch nvoOption1 _02;

network output SNVT_sw itch nvoOption1 _03;

network output SNVT_sw itch nvoOption2 _00;

network output SNVT_sw itch nvoOption2 _01;

network output SNVT_sw itch nvoOption2 _02;

network output SNVT_sw itch nvoOption2 _03;

These ou tput n e twork var i ables provide notif ication of ch anges in

the st atus of the indoor unit opt io n settings .

Two of the following 4 optio n s e t tin gs can be s e lect ed:

remote-contro ller prohibit, fan speed setting, air di rection setting,

and filter sign r e set.

Make ch anges using the DIP switc hes on the main circuit bo ard.

They are ou tput when th e LonW orks Interface or A/C unit pow er is

reset.

Temp.

setti ng

Operat i n

g mode

O

O

value

(No t us ed )

100

120

140

150

160

180

200

Fan speed

s e ttin g

Auto

Hi gh

Mediu m

Lo w

Sw in g

F1

F2

F3

F4

F5

Filter

sign

F ilter sign is reset w h e n

data is up date d .

F1

F2

F3

F4

F5

*

Positions F 4

and F5 can no t be

set for cool- a n d

dry-mode

operation .

state

0

1

Othe r

120

200

150

100

(Not

us ed )

Othe r

200

170

140

110

(Not

us ed )

Othe r

Sw in g

80

50

Operat i ng

mode

O

value

0

100

120

140

150

160

180

200

Remote-

controller

proh i b i t

Auto

Hi gh

Mediu m

Lo w

Sw in g

F1

F2

F3

F4

F5

state

0

1

120

200

150

100

1

50

200

170

140

110

1

0

Sto p

80

50

0

0

1

OFF

ON

Sto p

Ve r y

0

Remote-

controller

proh i b i t

Start/stop

ope rati on

O









O

O

O

O

Air

di rect i on

s e ttin g

Temp.
s e ttin g

Start/stop

ope rati on

O

O

O

O

Fan speed

s e ttin g

Air

di rect i on

s e ttin g

Filter

sign

O :Permitted

:

Prohibite d

O :Permitted

O

O























:Prohibited