7. LonWorks Interface product Manual (SHA-LN16UAB)

2

[nv11] Alarm notification

network output SNVT_sw itch nvoAlarm_00;

network output SNVT_sw itch nvoAlarm_01;

network output SNVT_sw itch nvoAlarm_02;

network output SNVT_sw itch nvoAlarm_03;

These ou tput n etwork var iables are output when an alarm occu rs at

an indoor unit, and when th e alarm is reset at an indoor unit.

They are ou tput when th e LonW orks Interface or A/C unit pow er is

reset.

Contents

state 0: Normal

value 0 at all times

1: Alarm

[nv12] Indoor unit number with active alarm notification

network output SNVT_sw itch nvoAlarmIn_00;

network output SNVT_sw itch nvoAlarmIn_01;

network output SNVT_sw itch nvoAlarmIn_02;

network output SNVT_sw itch nvoAlarmIn_03;

These ou tput n etwork var iables are output when an alarm occu rs at

an indoor unit.

They are ou tput when th e LonW orks Interface or A/C unit pow er is

reset.

Contents

state 0 at al l time s value Indoo r un it numbe r w i th

ac tiv e alar m 2

* Valu e = 0 w h en no a l arms a r e active.

[nv13] Room temperature notification

network output SNVT_temp_p nvoSpaceTemp_00;

network output SNVT_temp_p nvoSpaceTemp_01;

network output SNVT_temp_p nvoSpaceTemp_02;

network output SNVT_temp_p nvoSpaceTemp_03;

These outpu t network variables are ou tput w h en the indoor unit

room tem p eratur e ch anges .

They are ou tput when th e LonW orks Interface or A/C unit pow er is

reset.

When indoor u nits ar e und er g roup contro l, th e room temperature

of the m a in un it in th e group is o u tput.

Contents

Valid ra ng e

Output range:

-31 to 199°F (-35 - 92.5°C)

Temp. units:

1°F (0.5°C)

* Be aware that the output temperat ure r a nge may var y according to

the models of th e outdoor and in door units.

*When indoor u n its are under gr oup control, th e status is output f r om

the m a in unit .

[nv14] A/C unit status notification

network output SNVT_co unt nvoInS tate_0 0;

network output SNVT_co unt nvoInS tate_0 1;

network output SNVT_co unt nvoInS tate_0 2;

network output SNVT_co unt nvoInS tate_0 3;

These ou tput network va ri ables are ou tput when the A/C un it s t atus

changes.

They are ou tput when th e LonW orks Interface or A/C unit pow er is

reset.

[nv15] Emergency stop

network output SNVT_sw itch nviAllInOff;

This input network variab le is us ed to stop th e indoor units in an

emergency .

Rem o te-contro l l er prohibi t (sta rt/stop prohibi t) is en abled for the

stopped indoor u n its.

The rem o te- c ontroller proh ib it (t emperature set ting, op erating

mode) status r emains the same as before th e un its were stopped.

W h en em erge nc y s t op is c a n cel ed, r e mote- c ontroller prohibit

(start/stop prohi bit) st atus retur n s to the sta t us prior to em erg e nc y

stop; however , the unit itself remains stopped .

If th is fun c tio n is not used , t h en it is not n e cessar y to use t h is

network var iable.

Contents

state 0: Canc el

value (Not use d)

1: Emergenc y stop

[nc49] T ransmission interval setting

network input con fig SN VT_time_sec n c iS ndHrtBt;

This network configura tion se ts the inte rval for autom a t i c d a ta

output. When th e set time has elapsed, d a t a is ou tput autom a ti cal l y .

The ne twork variabl e s tha t ar e affe cted b y th is configuration are

the fo llowing:

nvoOnOff_0? nvoSetpoint_0? nvoHeatCool_0?

nvoOption1_0 ? nvoOption2 _0? nvoAlarm_0?

nvoAlarmIn_0 ? nvoSpaceT emp_0? nvoI nState_0?

Contents

The v a lid r a nge is 0 . 0 seco nds to 6553.5 s econds. If 0 .0 seconds

is set, au tomatic data update is disabled.

The tr ansm ission interva l s e tting is the sa m e for all n e tw ork

variables.

When the set time has elaps e d, above all n e twork variab les are

output.

[nc52] Setting of minimum time secured for transmission

network input con fig SN VT _time_sec n ciMinOutTm;

This network configuration determin es the m i ni m u m interval th at is

secured fo r outp u t network var i ables.

The n e twork v a riables tha t a r e a ffect ed b y this c onfiguration ar e the

following:

nvoOnOff_0? nvoSetpoint_0? nvoHeatCool_0?

nvoOption1_0 ? nvoOption2 _0? nvoAlarm_0?

nvoAlarmIn_0 ? nvoSpaceT emp_0? nvoI nState_0?

Contents

The v a lid rang e is 0.0 seconds to 6553.5 second s.

The m i nim u m tim e secured f o r transm ission is ind e pend ent for

each n e twork v a riabl e . It is no t val i d betw een differ e nt ne twork

variables.

No rma l c o m m un icatio n s in p r o g re ss ( n o alarm s )

A ccordin g to al arm code tab l e

0

1~ 255

300

Indoor un it not conn ected (initial

communic a tio n i n progr ess)

8. Locations Where Neuron ID is Applied

The Neuron ID is applied in the following 3 locations.

(1) Packaging box

(2) Top panel lid

(3) On the main circuit board Neuron chip

NeulonID

Node0 : 00 03 18 69 95 01

Node1 : 00 03 18 69 96 01

Node2 : 00 03 18 69 97 01

Node3 : 00 03 18 69 98 01

(2)

Main circuit board

Setting SW

Address

SW

Indoor unit

enabling

SW

IC002

00 03 18

69 95 01

Neuron ID

(3)

MiniECO-i.indb 135

2007/06/20 16:31:17