4-4

PCB and Functions

1. Outdoor Unit Control PCB

CN15

The control operations that are shown below are when you short-circuit this cooling inspection
pin located on the outdoor unit control PCB.

1.Thermistor inspection

Thermistor

Detection results

Normal

Error

Discharge temperature (TD)

LED1 lights up

LED1, 2 turns off

Outdoor temperature (TO)

LED2 lights up

Heat exchanger temperature (C1)

LED1 lights up

Heat exchanger temperature (C2)

LED2 lights up

Air inlet temperature (TS)

LED1 lights up

n

2. Turn ON the four-way valve for one second

3. Forced cooling operation

CN50

This pin is used to perform automatic address while operating the compressor. Normally,
automatic address can be performed in Heating mode, short-circuit this pin to perform
automatic address when operation is in Cooling mode.

CN33

3P plug (black): Terminal plug of the communications circuit

A connecting socket (2P, black) for short circuiting is attached to the terminal plug at the
time of shipment from the factory.
When multiple systems are operated in centralized control, leave the connecting socket in
place at only 1 of the outdoor unit in system address, and then replace the socket 2 to 3
from the outdoor unit (other than 1). If multiple connecting sockets are left in place while
operated in centralized control, communications trouble will occur.
When there is only single (system address 0) connecting socket of 1 system, do not remove
the connecting socket. (It is for the warning “ ”.)

CN028

2P plug (white): Silent mode operation pin

Operates the outdoor fan and compressor frequency with a limitation.
When relay turns ON, operating noise becomes low.

Silent
CN028

Relay
(field supply)

Power
source

External contact
(Timer input, etc.: field supply)

Outdoor unit control PCB
Note 1: Make the length of the wire between the outdoor unit control PCB to Relay within

6-9/16 ft.

2P socket with lead wire (Service parts: Parts code/623-161-2098)
Relay field supply contact input specification DC5V and 0.5mA
(Recommended relay; The Fuji Electric Co. /HH62SW nano-contact point
correspondence)
Use commercially available timer. (Omron “H5” daily time switch, etc.)