System controller (sha-kc64ug) – Sanyo CHX06052 User Manual

Page 76

Advertising
background image

2-58

Remote Control Functions

4. System Controller (SHA-KC64UG)

(c) Automatic zone registration using the system controller

(SHA-KC64UG)

(1) Press the

and

buttons at the same time for more than 4

seconds.

and CODE No. C1 will flash.

(2) Select CODE. No. C2 by pressing

and

(

) button

and press the

button.

C2 changes from flashing to ON state and automatic zone

registration will start.

(3) Any registered GROUP Nos. will be erased.
(4) Central address will be assigned from smallest indoor unit address

to larger ones in numerical order automatically.

On finishing automatic zone registration,

changes from flashing

to OFF.

(5) If an error occurs, “CHECK” starts flashing and zone

registration finishes at this time. Press the

button to start over.

(6) Finally, complete automatic zone registration mode by pressing the

button.

flashes for a few minutes, then turns OFF.

How to check for overlapping of central address Nos.

(1) Press the

and

buttons at the same time for more than 4

seconds.

and CODE No. C1 will flash.

(2) Select CODE. No. C3 by pressing

,

(

) button and

press the

button.

C3 changes from flashing to ON state and

will flash. Then

auto overlap checking will start.

(3) If C3 changes from ON to flashing and

stops flashing and

disappears, there is no overlapping.

Then finally, complete the auto overlap checking mode by pressing

the

button.

(4) If some of GROUP No., ZONE No. and UNIT No. flash, you should

try the zone registration again.

Select CODE No. C1 by pressing

,

(

) button and

press the

button.

Select the flashing GROUP No. with ZONE and GROUP button.

Then press the

button and reselect the ZONE, GROUP and

UNIT No.

Then finally, complete the auto overlap checking mode by

pressing the

button.

1

2

3