System controller (sha-kc64ug), Caution – Sanyo CHX06052 User Manual

Page 67

Advertising
background image

2-49

Remote Control Functions

4. System Controller (SHA-KC64UG)

2

Electrical Wiring

How to connect electrical wiring

For New Model (

**

52 Series)

(1) Connect B1, B2 to indoor PCB T10 connector using

the accessory 6P connector. (with fuse) (*No polarity)

Total wire length is less than 985 ft. and size is

AWG#18.

(2) Connect B5, B6 to indoor unit 2P terminal base.

(*No polarity). Wire size is AWG#18.

For Old Model (

**

42 Series)

(1) Connect B1, B2 to indoor PCB CRV connector using

the accessory 2P connector. (*No polarity)

Total wire length is less than 985 ft. and size is

AWG#18.

(2) Connect B5, B6 to indoor unit 2P terminal base.

(*No polarity). Wire size is AWG#18.

Basic wiring

Terminals for remote monitoring

Basic wiring diagram of control wiring

A max. of 64 indoor units and 30 outdoor units can

be connected in 1 system.

Up to 10 system controllers can be connected in

1 system.

B1

Indoor unit PCB

T10
(YEL)

2P terminal base

Indoor unit

System controller

Accessory connector

Wire joint connection

B2

B3

B4

B5

B6

U1

U2

B1

Indoor unit PCB

CRV
(WHT)

2P terminal base

Indoor unit

System controller

Accessory connector

Wire joint connection

B2

B3

B4

B5

B6

U1

U2

A1

<Back side of system controller>

A2

A3

A4

A5

A6

B6

B5

B4

B3

B2

B1

Inter-unit
control wiring

System controller

RC1

1-1

RC2

RC3

2-1

3-1

B1:

B2:

B3:

B4:

B5:

B6:

Power supply: DC12V *No polarity
To CRV connector (CN91)
or T10 connector on indoor PCB

Inter-unit control wiring. (Low voltage)
To indoor unit 2P terminal base (U1, U2)
*No polarity

Auxiliary of inter-unit control wiring

Not be used

A1:

A2:

A3:

Common input for turning air conditioners on or off.

A4:

A5:

A6:

ON operation state indicator output.

Alarm indicator output.

Common indicator output.

Input for turning off air conditioners concurrently.

Input for turning on air conditioners concurrently.

Basic wiring diagram

Ensure that wiring connections are correct. (Incorrect wiring will

damage the equipment.)

1. Lines consisting of dots and dashes (

) indicate inter-unit control

wirings.

2. In. means indoor unit.

3. Up to two system controllers may be connected to one control line system.

CAUTION

1 2

1 2

1 2

1 2

1 2

2

1 2

1

2

1 2

1

In.-1

In.-2

In.-3

In.-4

In.-n

C1

C2

C3

C4

L1

L2

C1

C2

C3

C4

L1

L2

2

1 2

1

1 2

2

1

2

1

Outdoor

unit-1

Outdoor

unit-2

Outdoor

unit-3

Outdoor

unit-m

Ground

Ground

Power supply

(

60 Hz, 208/230 V)

Ground for control wiring

System

controller

System

controller

Power supply

(

60 Hz, 208/230 V)

Ground for control wiring

Remote

controller

Remote

controller

Remote

controller

m : 30

Remote

controller

n : 64

1 2

1 2

1 2

1 2

NOTE

MiniECO-i.indb 49

2007/06/20 16:29:00