Check of density limit – Sanyo CHX06052 User Manual

Page 3

Advertising
background image

ii

2. The standards for minimum room volume are as

follows.

(1) No partition (shaded portion)

(2) When there is an effective opening with the

adjacent room for ventilation of leaking refrigerant
gas (opening without a door, or an opening 0.15%
or larger than the respective floor spaces at the
top or bottom of the door).

(3) If an indoor unit is installed in each partitioned

room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.

3. The minimum indoor floor space compared with the

amount of refrigerant is roughly as follows (when
the ceiling is 8.8 ft. high):

Check of Density Limit

The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws imposed
to protect the ozone layer. However, since it contains
more than air, it poses the risk of suffocation if its
density should rise excessively.
Suffocation from leakage of refrigerant is almost non-
existent. With the recent increase in the number of high
density buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power, etc.
Most importantly, the multi air conditioner system
is able to replenish a large amount of refrigerant
compared to conventional individual air conditioners.
If a single unit of the multi air conditioner system is to
be installed in a small room, select a suitable model
and installation procedure so that if the refrigerant
accidentally leaks out, its density does not reach the
limit (and in the event of an emergency, measures can
be made before injury can occur).
In a room where the density may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The density is as given below.

Total amount of refrigerant (oz)

Min. volume of the indoor unit installed room (ft.

3

)

Density limit (oz/ft.

3

)

The density limit of refrigerant which is used in multi air con-

ditioners is 0.3 oz/ft.

3

(ISO 5149).

NOTE

1. If there are 2 or more refrigerating systems in a

single refrigerating device, the amount of refrigerant
should be as charged in each independent device.

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in rooms A,
B and C is 353 oz.

The possible amount of leaked refrigerant gas in rooms D,
E and F is 529 oz.

Outdoor unit

Refrigerant tubing

Indoor unit

e.g., charged
amount (353 oz)

Outdoor unit

Indoor unit

Room A Room B Room C Room D Room E Room F

e.g., charged

amount (529 oz)

Refrigerant tubing

Outdoor unit

Very
small
room

Indoor unit

Small
room

Medium
room

Large room

Mechanical ventilation device - Gas leak detector

0

0

57

114

170

227

284

341

398

454

0

500

1000

1500

2000

2500

3000

3500

4000

400

200

600

800 1000 1200

Total amount of refrigerant

Min.

indoor

v

olume

Min.

indoor floor area

(when the ceiling is 8.8 ft.

high)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

MiniECO-i.indb 2

2007/06/20 16:27:54

Advertising