Troubleshooting & repair, Out of voltage range shut down test – Lincoln Electric NA-5S User Manual

Page 107

Advertising
background image

F-54

TROUBLESHOOTING & REPAIR

F-54

5. Start welding and observe the

ACTUAL voltage reading on the NA-
5 digital meter. The actual voltage
must match the SET voltage within
+/- 0.5VDC. If it does NOT, the NA-
5 is designed to shut down.

6. If the NA-5 continues to shut down

with the "BYPASS" pins jumpered
together, the voltage PC board may
be faulty.

7. If the ACTUAL voltage reading is

zero, the sensing leads may be
faulty. Perform the

External

Resistance Test. Also check the
1/8 amp fuse on the voltage PC
board.

8. Check the polarity switche in the

Lincoln power source and its associ-
ated leads. Set the switches to the
same polarity as the electrode. See
the Wiring Diagram.

9. If the ACTUAL voltage reading is dif-

ferent from the SET voltage reading,
the power source may not be capa-
ble of producing the required arc
voltage, the control cable may be
faulty or misconnected, or the NA-5
voltage PC board may be faulty.

10. After all tests are complete, remove

the input power to the wire feeder
and remove the jumper wire you
placed on the "BYPASS' pins on
the voltage PC board. Close and
secure the access door.

OUT OF VOLTAGE RANGE SHUT DOWN TEST

(Continued)

NA-5

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Advertising
This manual is related to the following products: