DIP Switch Setting on the Control Site

1. Set the WJ-NT204 Rear DIP Switch as follows. This set-

ting applies when connecting with PS

Data devices

such as System Controller on the Control site.

Bit # 1: ON/OFF Termination, set to ON at the chain

end of the RS-485 DATA line, other-
wise OFF.

Bit # 2: ON/OFF Termination, set to ON at the chain

end of the RS-485 DATA line, other-
wise OFF.

Bit

#

3: OFF

Straight wiring for RS-485 DATA
PORT

Bit # 4: OFF

RS-485 DATA port is selected.

Bit # 5: ON/OFF Termination, set to ON at the chain

end of the RS-485 HOST line, other-
wise OFF.

Bit # 6: ON/OFF Termination, set to ON at the chain

end of the RS-485 HOST line, other-
wise OFF.

ON

OFF

6

5

4

3

2

1

OFF: Open for Lines

ON: Termination for
RS-485 (PS.Data) Lines

System Controller
WV-CU360

8

7

0

9

8

7

6

5

4

3

2

1

Set the unit number

ON

OFF

6

5

4

3

2

1

OFF, OFF: Open for DATA Line

OFF: Straight wiring for RS-485 DATA PORT

ON, ON: Termination for DATA Lines

OFF: RS-485 DATA PORT selected

WJ-NT204 (Receiver)
SETUP DIP Switch

PC Connection

Connect the Remote site unit to the PC via a hub with Ethernet straight cables as shown below.
For more details, refer to LAN TYPE CONNECTION on page 66.

Connection to a Client PC via Hub

PC (browser)

Hub

Ethernet

straight cable

Ethernet

straight cable

WJ-NT204 Network

Interface Unit for remote site

Combination Cameras (4)

2. Set the DIP Switch and Unit Number Switch on the rear

of the System Controller WV-CU360 as follows. For
details refer to the manual included in the System
Controller.

DIP Bit #5:

ON/OFF

Termination for RS-485
(PS

DATA), set to ON at the

RS-485 chain end, otherwise
set to OFF.

Unit Number: Set to 1.