2 measurement of liquids, Flat vessel tops – VEGA VEGASON 51V…53V User Manual
Page 25
Advertising
VEGASON 51 V … 53 V
25
Reference pane
< 60 mm
Mounting and installation
-
Measurement of liquids
4.2 Measurement of liquids
Flat vessel tops
On flat vessels the mounting is mainly made
on a very short DIN-socket piece. Reference
pane on flange versions is the instrument
flange. The transducer should protrude out of
the flange pipe.
Flange version on very short DIN-socket piece
Very suitable is the mounting directly on the
vessel top. A round opening on the vessel is
sufficient to fasten VEGASON 53 sensor with
a compression flange.
Flange version (compression flange) on flat vessel
top
You can also mount the sensors with 1
1
/
2
" or
2" thread to short socket pieces.
Reference pane
Reference pane
Min.
distance
< 60 mm
Mounting on short 1
1
/
2
" or 2" socket piece