Set-up

-

Adjustment with PC on VEGAMET

• Plug the two small pin plugs of

VEGACONNECT 2 into the CONNECT-
socket of the signal conditioning instru-
ment.

• Now switch on the voltage supply of the

signal conditioning instrument.

After approx. 1…2 minutes (selfcheck) the
meas. system is generally ready for opera-
tion and indicates measured values.

• Now start the adjustment software VVO on

your PC.

• Choose in the entrance screen with the

arrow keys or the mouse the item "

Plan-

ning" and click to "OK".

In the next window you are asked for the
user identification.

• Enter under the name "VEGA".
• Also enter under the password

"VEGA".

The adjustment program, just called VVO,
gets in contact with connected coordination/
sensor...... and indicates after a few seconds
if and with which coordination/sensor a con-
nection exists.
The preadjusted identification can be modi-
fied later in the menu "User access".

Note:

If you do not get a sensor connection, please
check:
- is the sensor fed with power supply (min.

20 V)?

- do you use an older VEGACONNECT

instead of the new VEGACONNECT 2 ?

If VVO (adjustment software) gets in contact
with the signal conditioning instrument for the
first time, you are asked if the data should be
transferred from the signal conditioning in-
strument to the PC.

• Click to "

Yes"

In the following menu window "

DISBUS-group

choice" you can give a name to the database
or keep the suggested file name.