Set-up
-
Adjustment with PC on VEGALOG
• Enter under name "VEGA".
• Also enter under password
"VEGA".
The adjustment program, called in the follow-
ing VVO, contacts the connected Meas.
system/sensor …… and shows after a few
seconds if and with which Meas. system/
Sensors a connection exists.
Note:
If you do not get a sensor connection, check
the following:
- is the processing system powered with
supply voltage?
- do you erroneously use a wrong RS232-
cable instead of the VEGA RS-232-connec-
tion cable?
If VVO (adjustment software) contacts the
processing system for the first time, you are
asked if the data should be transferred from
the processing system to the PC.
• Click to "Yes"
When you connect VVO to a VEGALOG
where data have been already saved, a
message is displayed whether you want to
transfer the saved data from the PC to
VEGALOG or whether the data of VEGALOG
should be transferred to the PC.
• Click to "
OK", and you are in the main menu
window.
The preadjusted identification can be modi-
fied later in the menu "
Configuration/Program/
User access" (see page 43 right column).