Sensor too close to the vessel wall, Mounting and installation - installation error – VEGA VEGASON 51V…53V User Manual

Page 36

Advertising
background image

36

VEGASON 51 V … 53 V

Mounting and installation

-

Installation error

Sensor too close to the vessel wall

Sensor too close to the vessel wall

1 m

2 m

3 m

4 m

5 m

5 m

10 m

15 m

B

A

Max. meas.
distance

Distance of the
transducer to the
vessel wall

Curve 1 (liquids)

Curve 2 (solids)

If the sensor is mounted too close to the
vessel wall (dimension A in diagram) strong
false echoes can be caused. Build-up, rivets,
screws and weld joints superimpose their
echoes to the product echo or useful echo.
Hence note a sufficient distance of the sensor
to the vessel wall dependent on the max.
meas. distance (dimension B in diagram). In
case of good reflection conditions (liquids, no
vessel installation) we recommend to provide
the sensor distance according to

diagram

curve 1

. At a max. meas. distance of e.g.

10 m the distance of the transducer accord-
ing to curve 1 would be approx. 1 m.

In case of solids with bad reflection condi-
tions provide a distance to the vessel wall
according to

diagram curve 2

. With very

bad meas. conditions it can be necessary to
increase the distance to the vessel wall or to
gate out the false echoes additionally by a
false echo storage and hence to adapt the
sensor more precisely to the environment.

Correct

Wrong