VEGA VEGASON 51V…53V User Manual
Page 52
52
VEGASON 51 V … 53 V
Sensor optimisation
In the menu "
Sensor optimisation" you can
carry out special optimizing adjustments of
the sensors and can optimize e.g. by means
of the echo curve the installation position of
the sensor.
Meas. environment
• Choose the menu
"Instrument data/Parameter adjustment"
• Choose in the menu window "Instrument
data parameter adjustment" the menu point
"Sensor optimisation", and click to "Sensor
A"
• First click to "Meas. environment".
• Choose "
scaled", "Volume" when the indi-
cation should display e.g. litres. In the
example a level of 45 … 1200 litres would
be displayed.
• Enter the meas. distance in metres which
you have entered in the min./max. adjust-
ment and the appropriate litre information
corresponding to the min. and the max.
value.
• Click to
"Save"
• Click in the window "
Sensor display" to
"Quit"
• Click in the menu window "Display of meas-
ured value” to "Quit".
You are now again in the menu window "
Out-
puts"
• Click to
"Quit" in the menu window
"
Outputs"
You are again in the menu window "
Instru-
ment data parameter adjustment".
Set-up
-
Adjustment with PC on VEGAMET