The window "

Meas. environment" opens

With the menu point "

Measuring range" you

can define the measuring range of the sensor
deviating from the "

Min/Max-Adjustment".

As a standard feature the measuring range
normally corresponds to the min./max. ad-
justment.

Generally it will be suitable to choose the
measuring range approx. 5 % larger than the
range determined by the min./max. adjust-
ment.
In the example the min. adjustment was at
0,500 m and the max. adjustment at 3,400 m.
In the example you would adjust the measur-
ing range to 0,4 … 3,5 m.

• Save the adjustments with "OK"

• Click in the menu window "

Meas. environ-

ment" to "Measuring condition".

• In the menu window "

Measuring conditions"

you click to the options corresponding to
your application.

• Confirm with "OK".
After some seconds of saving during which
the adjustments are saved in the sensor, you
are again in the window "

Meas. environment".

• Click in the menu window "

Meas. environ-

ment" to "Quit".

You are again in the menu window "

Sensor

optimisation".

Echo curve

With the menu point "

Echo curve" you can

look at the course and the strength of the
detected ultrasonic echo.

If due to vessel installations, strong false
echoes have to be expected, a correction of
the installation position (if possible) can help
to localize and reduce the size of the false
echo by monitoring the echo curve.

Set-up

-

Adjustment with PC on VEGAMET