Fig. 6: Measurement setup, flow measurement in vapours with VEGADIF 55
1
Condensate vessels
2
Orifice or impact pressure probe
3
Block valves
4
VEGADIF 55
5
Precipitator
6
Drain valves
7
Three-fold valve block
à Mount VEGADIF 55 below the measurement loop
à Mount condensate vessels at the same height with the discharge
socket and at the same distance to VEGADIF 55
à Fill the effective pressure lines to the height of the condensate
vessels before setup
Flow measurement in
vapours
VEGADIF
55 • 4 … 20
mA/HART