3 mounting instructions for level measurement – VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 15
4
.3 Mounting instructions for level measurement
+
p
atm
min.
p
atm
1
2
3
4
5
Fig. 8: Measurement setup, level measurement in the open vessel
1
Minus side is open to the atmospheric pressure
2
VEGADIF 55
3
Block valve
4
Precipitator
5
Drain valve
à Mount VEGADIF 55 below the lower measurement connection so
that the effective pressure lines are always filled with liquid
à Minus side is open to the atmospheric pressure
+
–
min.
p
atm
p
atm
1
2
Fig. 9: Measurement setup, level measurement in the open vessel
1
VEGADIF 55
2
Minus side is open to the atmospheric pressure
à Mount VEGADIF 55 directly to the vessel
à Minus side is open to the atmospheric pressure
Level measurement in
the open vessel with
effective pressure line
Level measurement in
the open vessel with
flange
VEGADIF
55 • 4 … 20
mA/HART
15
4 M
ounting
31731
-EN
-081119