VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 63

Advertising
background image

1)

2)

1)

1)

MAX FLOW

MAX. PRESS. FLOW

DAMPING VALUE

POS. ZERO ADJUST

MEASURING MODE

OPERATING MENU

QUICK SETUP

Measured value

LANGUAGE

GROUP SELECTION

Flow

Pressure

Level

MEASURING MODE

1

Indication only via local indication

2

Indication only via HART handheld

Measured value indication: M

ove with "E" from the measured value

presentation to the GROUP SELECTION.

GROUP SELECTION: S

elect parameter MEASURING MODE.

MEASURING MODE: S

elect option "Flow".

GROUP SELECTION: S

elect Quick SETUP menu.

POS. ZERO ADJUST: D

ue due the installation position of the

instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE

via the parameter POS. ZERO ADJUST with the

option "Accept", i.e. assign the value 0 to the existing pressure.

MAX. FLOW: E

nter the max. flow of the effective pressure transmitter

(

see also construction sheet of the effective pressure transmitter).

MAX. PRESSURE: E

nter the max. pressure of the effective pressure

transmitter (see also construction sheet of the effective pressure

transmitter).

DAMPING VALUE: E

nter the damping time (time constant τ). The

damping influences the speed with which all following elements such

as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).

Local adjustment

VEGADIF

55 • 4 … 20

mA/HART

63

7 S

et up

31731

-EN