VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 51

Advertising
background image

Reset code

Description

7864

Total reset
T

his reset resets the following parameters:

l Function group POSITION ADJUSTMENT
l Function group BASIC SETUP
l Function group EXT. SETUP
l Function group LINEARIZATION (an existing linearization chart may be deleted)
l Function group: TOTALIZER SETUP
l Group OUTPUT
l Function group HART DATA
l Function group MESSAGES
l All messages to be configured (type "Error") are set to "Warning", see also Supplementary

instruction manual "Service instructions VEGADIF 55", "Messages" and chapter "Fault
rectification
"

l Function group USER LIMITS
l Function group SYSTEM 2
l If a simulation is running, this will be terminated
l The instrument carries out a restart

8888

Data memory module reset
M

easured value and event memory will be deleted. The data memory module must be plugged to

the electronics module during the reset.

E

xample LEVEL MODE = linear and LIN. MEASURAND = Height

l

HEIGHT UNIT =

m

l

CALIBRATION MODE =

wet

l

EMPTY CALIB. = 0

l

FULL CALIB. = S

ensor final value converted in H²O, e.g. with a

500

mbar sensor: 5.99 mH²O

VEGADIF

55 • 4 … 20

mA/HART

51

6 O

peration

31731

-EN

-081119

Advertising