POS. ZERO ADJUST: D

ue due the installation position of the

instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE

via the parameter POS. ZERO ADJUST with the

option "Accept", i.e. assign the value 0 to the existing pressure.

EMPTY CALIB.: E

nter the level value for the lower adjustment point.

F

or this parameter, you enter a level value assigned to the pressure

acting on the instrument. Enter level value for the lower adjustment
point. Prerequisites: Level selection "Level Easy Pressure", Calibra-
tion mode "wet"; Level selection "Level Standard", Level mode "linear"
and Calibration mode "wet"

FULL CALIB.: E

nter the level value for the upper adjustment point. For

this parameter, you enter a level value assigned to the pressure acting
on the instrument. Enter level value for the upper adjustment point.
P

rerequisites: Level selection "Level Easy Pressure", Calibration

mode "wet"; Level selection "Level Standard", Level mode "linear" and
C

alibration mode "wet"

DAMPING VALUE: E

nter the damping time (time constant τ). The

damping influences the speed with which all following elements such

as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).

Measured value indication: S

elect Quick SETUP menu

MEASURING MODE: S

elect option "Level".

Level selection: S

elect level mode.

POS. ZERO ADJUST: D

ue due the installation position of the

instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE

via the parameter POS. ZERO ADJUST with the

option "Accept", i.e. assign the value 0 to the existing pressure.

EMPTY CALIB.: E

nter the level value for the lower adjustment point.

F

or this parameter, you enter a level value assigned to the pressure

acting on the instrument. Enter level value for the lower adjustment
point. Prerequisites: Level selection "Level Easy Pressure", Calibra-
tion mode "wet"; Level selection "Level Standard", Level mode "linear"
and Calibration mode "wet"

FULL CALIB.: E

nter the level value for the upper adjustment point. For

this parameter, you enter a level value assigned to the pressure acting
on the instrument. Enter level value for the upper adjustment point.
P

rerequisites: Level selection "Level Easy Pressure", Calibration

mode "wet"; Level selection "Level Standard", Level mode "linear" and
C

alibration mode "wet"

DAMPING VALUE: E

nter the damping time (time constant τ). The

damping influences the speed with which all following elements such

as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).

Note:
F

or local adjustment see also "Operating elements".

HART handheld

VEGADIF

55 • 4 … 20

mA/HART