Fig. 7: Measurement setup, flow measurement in liquids with VEGADIF 55
1
Orifice or impact pressure probe
2
Block valves
3
VEGADIF 55
4
Precipitator
5
Drain valves
6
Three-fold valve block
à Mount VEGADIF 55 below the measurement loop so that the
effective pressure lines are always filled with liquid and gas
bubbles can bubble up to the process line
à For measurements in products with solid content such as e.g. dirty
liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.
à Fill the effective pressure lines to the height of the condensate
vessels before setup
Flow measurement in
liquids