Information:
T

he adjustment must be unlocked. See also chapter "Lock/Unlock

adjustment".

1

S

eparate instrument from voltage supply

2

P

lug the data memory module into the electronics module.

C

onfiguration data of a different instrument are saved in the data

memory module.

3

C

onnect instrument again to voltage supply

4

Y

ou select via the parameter DOWNLOAD SELECT which

parameter should be overwritten (menu path: "Group selection -
Operating menu - Operating
")

D

epending on the selection, the following parameters are over-

written:

Copy config.: All parameters except DEVICE SERIAL NO.,
DEVICE DESIGN., CUST. TAG NUMBER, LONG TAG NUMBER,
DESCRIPTION, BUS ADDRESS

and the parameters of group

POSITION ADJUSTMENT

and PROCESS CONNECTION.

Instrument change: A

ll parameters except DEVICE SERIAL NO.,

DEVICE DESIGN.

and the parameters of group POSITION

ADJUSTMENT

and PROCESS CONNECTION

Electronics exchange: A

ll parameters except the parameters of

group POSITION ADJUSTMENT. Factory setting: Copy config.

5

S

elect via the parameter HistoROM CONTROL the option

"

HistoROM - Instrument"

for the transmission direction (menu

path: "Group selection - Operating menu - Operating").

6

W

ait approx. 20 sec. Configuration data are loaded from the data

memory module to the instrument. The instrument carries out a
restart.

7

B

efore you remove the data memory module from the electronics

module, you have to separate the instrument from the voltage
supply

VEGADIF

55 • 4 … 20

mA/HART

47

6 O

peration

31731

-EN

-081119