VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 37
l
"+" key and "-" key
-
Q
uit editing mode without saving the modified value
-
I
n the menu you are within a function group: when pushing the
keys for the first time simultaneously, you jump one parameter
back within the function group. With every further simulta-
neous pushing you jump one level in the menu to the top
-
Y
ou are in the menu on a selection level: With every
simultaneous pushing you jump one level in the menu to the
top
l
DIP
switch 1
-
T
o lock/unlock measured value-relevant parameters. Default
setting: off (unlocked)
l
DIP
switch 2
-
D
amping on/off, default setting: on (damping on)
6
.4 Local adjustment - local indication not
connected
Information:
F
or adjustment of the instrument with a data memory module see
"
Data memory module".
I
f no local indication is connected, the following functions will be
possible via the three keys on the electronics module or outside on the
instrument:
l
P
osition adjustment (zero point correction)
l
S
et measurement begin and measurement end
l
I
nstrument reset, see chart in chapter "Operating elements"
Information:
T
he adjustment must be unlocked, see chapter "Lock/Unlock adjust-
ment".
B
y default, the instrument is set to mode Pressure. The mode can be
changed via the parameter "Measuring Mode", see chapter "Select
language and measuring mode".
T
he existing pressure must be within the nominal pressure limits of the
sensor, see specifications on the "Type label".
Carry out position adjustment:
1
P
ressure on the instrument
2
P
ush "E" key at least for 3 s
3
D
oes the LED on the electronics module light briefly?
Y
es: existing pressure was accepted as position adjustment
N
o: Existing pressure for position adjustment was not accepted,
note the adjustment limits
Set LRV:
Measuring Mode - Pres-
sure
VEGADIF
55 • 4 … 20
mA/HART
37
6 O
peration
31731
-EN
-081119