Page 30: Test, 4 take 4 … 20 ma test signal

Advertising
background image

5

.4 Take 4 … 20 mA test signal

W

ithout interrupting the measurement you can tap a 4 … 20 mA test

signal via the plug and test terminal. By simply switching the bridges,
you can lower the min. supply voltage of the measuring instrument.
T

hrough this it also possible to operate the instrument with a weaker

voltage source. To keep the measurement error below 0.1 %, the
current meter should show an inner resistance of < 0.7 Ω. Take note of
the bridge position according to the following illustrations.

Test

Test

Fig. 28: Left: Position position of the bridge without test signal. Min. supply
voltage 10.5 V DC. Right: Position of the bridge with test signal. Min. supply
voltage 11.5 V DC.

5

.5 Load

1

2

30

20

10,5

U

[V]

40

45

1282

1500

847

413

Test

3

4

RLmax

RLmax

U - 10,5 V

23 mA

[ ]

30

20

11,5

U

[V]

40 45

1239

1456

804

369

Test

3

4

RLmax

U - 11,5 V

23 mA

RLmax

[ ]

Fig. 29: Load diagrams: Note position of the bridge and flame proofing. RLmax
max. load resistance, U voltage supply
1

Bridge for 4 … 20 mA test signal plugged in position "Non-test"

2

Bridge for 4 … 20 mA test signal plugged in position "Test"

3

Voltage supply 10.5 (11.5) … 30 V DC for EEx ia, 1/2 D, 1 GD, 1/2 GD, FM
IS and CSA IS

4

Supply voltage 10.5 (11.5) … 45 V DC for instruments for Ex-free area, 1/
3

D, EEx d, EEx nA, FM XP, FM DIP, FM NI, CSA XP and CSA Dust-Ex

5

.6 Connection control

C

heck the following after electrical installation of the instrument:

l

D

oes the supply voltage correspond to the specification on the

type label?

30

VEGADIF

55 • 4 … 20

mA/HART

5 C

onnecting to power supply

31731

-EN

-081119