Copy configuration data from a data memory module to an
instrument:

Information:
T

he adjustment must be unlocked. See also chapter "Lock/Unlock

adjustment".

1

S

eparate instrument from voltage supply

2

P

lug the data memory module into the electronics module.

C

onfiguration data of a different instrument are saved in the data

memory module.

3

C

onnect instrument again to voltage supply

4

P

ush "E" and "+" keys (at least 3 seconds) until the LED on the

electronics module lights

5

W

ait approx. 20 seconds. All parameters except DEVICE SERIAL

NO., DEVICE DESIGN., CUST. TAG NUMBER, LONG TAG
NUMBER, DESCRIPTION, BUS ADDRESS

and the parameters of

the group POSITION ADJUSTMENT and PROCESS CONNEC-
TION

are loaded from the data memory module in the instrument.

T

he instrument carries out a restart.

6

B

efore you remove the data memory module from the electronics

module, you have to separate the instrument from the voltage
supply

Copy configuration data from one instrument into a data memory
module:

Information:
T

he adjustment must be unlocked. See also chapter "Lock/Unlock

adjustment".

1

S

eparate instrument from voltage supply

2

P

lug data memory module into the electronics module

3

C

onnect instrument again to voltage supply

4

T

he selection for the parameter DOWNLOAD SELECT does not

influence an upload from the instrument in HistoROM (menu

path:"Group selection - Operating menu - Operating"

5

S

elect via the parameter HistoROM CONTROL the option

"

Instrument - HistoROM"

for the transmission direction (menu

path: "Group selection - Operating menu - Operating").

6

W

ait approx. 20 seconds. Configuration data are loaded from the

instrument to the data memory module. The instrument does not
carry out a restart.

7

S

eparate instrument again from voltage supply

8

R

emove memory module

9

C

onnect instrument again to voltage supply

Copy configuration data from a data memory module to an
instrument:

Local adjustment
through local indication
(optional) or remote ad-
justment

46