VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 18

Advertising
background image

Information:
L

evel measurement is only ensured between the upper edge of the

lower and the lower edge of the upper pressure transmitter.

+

min.

max.

1

2

2

3

4

6

5

5

Fig. 13: Measurement setup in closed vessel with superimposed steam
1

Condensate vessel

2

Block valves

3

VEGADIF 55

4

Precipitator

5

Drain valves

6

Three-fold valve block

à Mount VEGADIF 55 below the lower measurement connection so

that the effective pressure lines are always filled with liquid

à Connect minus side always above the max. level
à The condensate vessel ensures a constant pressure on the minus

side

à For measurements in products with solid content such as e.g. dirty

liquids, the installation of separators and drain valves is
recommended to enable collection and removal of debris and
sediment.

Level measurement in
closed vessel with
steam layer with effec-
tive pressure line

18