5 flow measurement – VEGA VEGADIF 55 4 … 20 mA_HART User Manual
Page 59
Parameter
name
Description
S
et value (563)
E
ntry
I
nput position adjustment - the pressure difference betwen
zero (set value) and measured pressure must not be known
(
there is a reference pressure on the instrument).
Example:
l MEASURED VALUE = 0.5 mbar
l For the parameter POS. INPUT VALUE you enter the
requested set value for the MEASURED VALUE, e.g.
2
mbar (valid: MEASURED VALUEnew = POS. INPUT
VALUE)
l MEASURED VALUE (after pos. zero adjust) = 2 mbar
l The parameter CALIB. OFFSET shows the resulting
pressure difference (offset) by which the MEASURED
VALUE
was corrected. This applies: CALIB. OFFSET =
MEASURED VALUE
old - POSITION POS. INPUT
VALUE,
here: CALIB. OFFSET = 0.5 mbar -2 mbar =
-1.5
mbar)
l The current value is also corrected
l Default setting 0
P
osition offset
(319)
E
ntry
I
nput position adjustment - the pressure difference between
zero (set value) and measured pressure is known (there is a
reference pressure on the instrument).
Example:
l MEASURED VALUE = 2.2 mbar
l Via the parameter CALIB. OFFSET you enter the value by
which the MEASURED VALUE should be corrected. To
correct the MEASURED VALUE to 0 mbar, you have to
enter the value 2.2 (valid: MEASURED VALUEnew =
MEASURED VALUE
old - CALIB. OFFSET)
l MEASURED VALUE (after adjustment for calib. offset) =
0
mbar
l The current value is also corrected
Factory setting
l 0
7
.5 Flow measurement
Note:
N
ormally, VEGADIF 55 is used in the basic version for flow
measurements.
B
efore adjusting VEGADIF 55, you have to clean the effective
pressure lines and the instrument must be filled with the medium.
Preparations
VEGADIF
55 • 4 … 20
mA/HART
59
7 S
et up
31731
-EN
-081119