VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 77

Advertising
background image

MEASURING MODE: S

elect option "Pressure".

GROUP SELECTION: S

elect QUICK SETUP menu.

POS. ZERO ADJUST: D

ue due the installation position of the

instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE

via the parameter POS. ZERO ADJUST with the

option "Accept", i.e. assign the value 0 to the existing pressure.

SET LRV: S

et measuring range (enter 4 mA value). Enter pressure

value for the lower current value (4 mA value). A reference pressure on
the instrument is not necessary. Set measuring range (enter 4 mA
value).

SET URV: S

et measuring range (enter 20 mA value). Enter pressure

value for the upper current value (20 mA value). A reference pressure
on the instrument is not necessary. Set measuring range (enter 20 mA
value).

DAMPING VALUE: E

nter the damping time (time constant τ). The

damping influences the speed with which all following elements such

as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).

Measured value indication: S

elect Quick SETUP menu.

MEASURING MODE: S

elect option "Pressure".

POS. ZERO ADJUST: D

ue due the installation position of the

instrument, a shift of the measured value can be caused. Correct the
MEASURED VALUE

via the parameter POS. ZERO ADJUST with the

option "Accept", i.e. assign the value 0 to the existing pressure.

SET LRV: S

et measuring range (enter 4 mA value). Enter pressure

value for the lower current value (4 mA value). A reference pressure on
the instrument is not necessary. Set measuring range (enter 4 mA
value).

SET URV: S

et measuring range (enter 20 mA value). Enter pressure

value for the upper current value (20 mA value). A reference pressure
on the instrument is not necessary. Set measuring range (enter 20 mA
value).

DAMPING VALUE: E

nter the damping time (time constant τ). The

damping influences the speed with which all following elements such

as e.g. local indication, measured value and current output react to a
pressure change. Enter the damping time (time constant τ).

HART handheld

VEGADIF

55 • 4 … 20

mA/HART

77

7 S

et up

31731

-EN

-081119