5 local adjustment – local indication connected, 5 local adjustment - local indication connected – VEGA VEGADIF 55 4 … 20 mA_HART User Manual

Page 40

Advertising
background image

2

P

ush "E" key at least for 3 s

3

D

oes the LED on the electronics module light briefly?

Y

es: existing pressure was accepted as position adjustment

N

o: Existing pressure for position adjustment was not accepted,

note the adjustment limits

Adjust max. pressure value:

1

R

equested pressure for max. pressure value (MAX. PRESSURE

FLOW)

is on the instrument

2

P

ush "+" key at least for 3 s

3

D

oes the LED on the electronics module light briefly?

Y

es: Existing pressure was saved as max. pressure value (MAX.

PRESSURE FLOW)

and assigned to the max. flow value (MAX.

FLOW).

N

o. Existing pressure for measurement begin was not saved as

max. pressure value. Note the adjustment limits

6

.5 Local adjustment - local indication connected

I

f the local indication is connected, the three adjustment key are used

for navigation in the adjustment menu, see chapter "Function of the
operating elements
".

T

he menu is divided into four levels. The three upper levels are used

for navigation whereas on the lowest level, numerical values are
entered, options selected and saved. The complete menu is shown in
chapter "Menu schematic". The "Adjustment menu" is composed
according to the selected mode, e.g. when the mode "Pressure" is
selected, only the functions necessary for this mode are displayed.

T

he parameters LANGUAGE and MODE are shown via the local

indication on the 1. selection level. Via the digital communication, the
parameter LANGUAGE is shown in group INDICATION and the
parameter MODE in the function group BASIC ADJUSTMENT.

Configuration of the
menu

40

VEGADIF

55 • 4 … 20

mA/HART

6 O

peration

31731

-EN

-081119