2 common specifications (continued), Indication, Environment – GE Industrial Solutions AF-300 G11 User Manual

Page 127

Advertising
background image

11-4

Data subject to change without notice 7/07. © 2007 GE Drives

11.2 Common Specifications (continued)

Explanation

Output frequency, setting frequency, output current, output voltage, motor synchronous speed,
line speed, load rotation speed, calculated PID value, PID command value, PID feedback value,
alarm code.

Operation information, operational guide, functional code/name/setting data, alarm information,
tester function, motor load rate measuring function (Maximum/average current (rms) during
measuring period, maintenance information (integrated operation hours, capacitance
measurement for main circuit capacitors, heatsink temperature, etc.

Six languages (Japanese, English, German, French, Spanish, Italian)

Charging (voltage residual), operation indication

Overcurrent, short-circuit, ground fault, overvoltage, undervoltage, overload, overheating, blown
fuse, motor overload, external alarm, input open-phase, output open0phase (when tuning),
braking resistor protection, CPU and memory error, keypad panel communications error, PTC
thermistor protection, surge protection, stall prevention, etc.

Indoor, altitude less than 3300 feet (1000m), free from corrosive gas, dust and direct sunlight.

-10 to +50°C (+14 to 122°F) (ventilating cover must be removed under conditions exceeding +40°C
(+104°F) for models rated at 30 HP or less)

3mm peak from 2-9 Hz, 9.8 m/s

2

from 9-20 Hz, 2m/s

2

from 20-55 Hz, 1 m/s

2

from 55-200 Hz,

Storage

Ambient
temperature

-25 to 65°C (-13 to 149°F)

Ambient
humidity

5 to 95% (no condensation)

Lamp display

Protective function

Indication

Item

Liquid crystal display

Digital display LED

Language

Installation location

Ambient temperature

Vibration

Environment

Advertising