GE Industrial Solutions AF-300 G11 User Manual

Page 142

Advertising
background image

12-7

Data subject to change without notice 7/07. © 2007 GE Drives

Type

Generation

Series

Voltage series

Data 4 Data 3 Data 2

Data 1

(All bit are ON or active by 1)

FWD:

Forward operation

IL:

Current limiting

REV:0: Reverse operation

ACC:

Under acceleration

EXT:

DC braking active (or pre-excitation) DEC:

Under deceleration

ALM:

Drive fault

INT:

No Output

RL:

Transmission valid

BRK:

Braking active

WR:

Function writing privlege

NUV:

DC link voltage is established

0: Keypad panel

(undervoltage at 0)

1: RS485

TL:

Torque limiting

2: Fieldbus (option)

VL:

Voltage limiting

BUSY: Processing data write

Data format [17]

Type code

Code

Type

Generation

Series

Voltage series

1

-

G11

-

-

2

G

-

-

-

3

P

-

-

230V three phase

4

-

-

-

460V three phase

5

-

-

USA

575V three phase

6

-

-

-

-

Data format [18]

Code setting (1–4 figures)

Data format [19]

Amperage value Decimal data (positive ):
Min. unit 0.01 inverter capacity is not more than 30HP
Min unit 0.01 for not less than 40HP

Example) If F11 (electronics thermal overload relay 1 level)107.0A (40HP)

107.0 X 10=1070=042E

H

If F11 (electronics thermal overload relay 1 level)=3.60A (1HP)
Since 3.60 X 100=360=0168

H

Data format [20]

Transmission error code

Code

Description

Code

1

FC (function code) error

71

CRC error

(no response)

2

Illegal address

72

Parity error

(no response)

3

Illegal address (Data range error)

73

Other errors

(no response)

-Framing error
-Overrun error
-Buffer full error

7

NAK
-Priority for comm
-No privilege for writing error
-Forbidden writing error

Description

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0