Pattern operation cycle operation completed (to), Pattern operation stage number (stg1)(stg2)(stg4), Alarm detail (al1)(al2)(al4)(al8) – GE Industrial Solutions AF-300 G11 User Manual

Page 77: Cooling fan operating (fan), Retry function operating (try), Universal do(u-do), Heat sink overheat early warning (oh), 2nd freq. level detection (fdt2), 2nd ol level early warning (ol2), Terminal c1 off signal (c1off)

Advertising
background image

5-24

Data subject to change without notice 7/07. © 2007 GE Drives

Pattern operation cycle operation completed
(TO)

Value 17: After the seven stages of a pattern operation
have been completed, this function outputs a one-shot,
100 ms ON signal to report the completion of all stages.

Pattern operation stage number

(STG1)(STG2)(STG4)

Value 18, 19, 20: During pattern operation, this function
reports the stage (operation process) being operated.

Pattern

Operation

Stage No.

STG1

STG2

STG4

Stage 1

on

off

off

Stage 2

off

on

off

Stage 3

on

on

off

Stage 4

off

off

on

Stage 5

on

off

on

Stage 6

off

on

on

Stage 7

on

on

on

Output Terminal

When pattern operation is not activated (i.e., no stage has
been selected), the terminals do not output a signal.

Alarm detail (AL1)(AL2)(AL4)(AL8)

Value 21, 22, 23, 24: This function reports the operating
status of the drive protective function.

Alarm Detail

(Drive Protective Function

AL1 AL2 AL4 AL8

Overcurrent, ground fault, blown fuse

on

off

off

off

Overvoltage

off

on

off

off

Undervoltage shortage, input phase
failure

on

on

off

off

Motor 1 and Motor 2 overload

off

off

on

off

drive overload

on

off

on

off

Heat sink overheating, drive
overheating internally

off

on

on

off

External alarm input, braking resistor
overheating

on

on

on

off

Memory error, CPU error

off

off

off

on

Keypad panel communication error,
option communication error

on

off

off

on

Option error

off

on

off

on

Output wiring error

off

off

on

on

RTU communication error

on

off

on

on

Overspeed, PG disconnection

off

on

on

on

Output Terminal

Under normal operation, terminals do not output a signa

Cooling fan operating (FAN)

Value 25: When used with H06 Cooling fan ON/OFF
control, this function outputs a signal while the cooling fan
is operating.

Retry function operating (TRY)

Value 26: When H04 Retry operating is set to 1 or higher,
the signal is output during the retry operation, if the drive
protective function has been activated.

Universal DO(U-DO)

Value 27: Assigning a value of 27 to a transistor output
terminal renders the terminal a universal DO terminal.

This function enables ON/OFF through the RS485 and
BUS option.

This function serves only to turn the transistor output on
or off through communication and is not related to drive
operation.

Heat sink overheat early warning (OH)

Value 28: This function outputs an early warning signal
when the heat sink temperature (overheat detection level)
is within 10

°

C of the overtemp trip point.

Synchronization completed by synchronous
operation card (SY)

Value 29: This is the synchronization complete signal for
the synchronize operation option. See Option Instruction
Book for details.

2nd Freq. level detection (FDT2)

Vallue 31: This function sets the 2nd Freq. level detection.
See the explanation of Function Code E36 and E37
Hysteresis width is same as FDT1 (E32).

2nd OL level early warning (OL2)

Value 32: This function sets the 2nd overload early
warning. See the explanation of “overload early warning
(OL)”, E37.

Terminal C1 off signal (C1OFF)

Value 33: This function outputs an ON signal, when the
C1 current input is smaller than 2mA.

SETTINGS WHEN SHIPPED FROM THE FACTORY

Digital Output

Value

Description

Terminal Y1

0

Operating (RUN)

Terminal Y2

1

Frequency arrival (FAR)

Terminal Y3

2

Frequency detection (FDT)

Terminal Y4

7

Overload early warning (OL)

Terminal Y5

15

Terminal AX function (AX)

Factory Setting at Shipment

E25 Y5 Ry operation mode

E 2 5

Y 5 R Y

M O D E

This function specifies whether to excite the Y5 relay at
“ON signal mode” or “OFF signal mode”

Set Value

Operation

0

At “OFF signal mode” Y5A - Y5C: OFF

At “ON signal mode” Y5A - Y5C: ON

1

At “OFF signal mode” Y5A - Y5C: ON

At “ON signal mode” Y5A - Y5C: OFF

Advertising