(2) Control circuit terminals

30A

Y5A CMY

Y3

Y1

C1

FMA FMP PLC

X1

X2

X3

X4

X5

X6

X7

X8

X9

30C

30B Y5C

Y4

Y2

11

12

13

V2

CM

CM FWD REV P24

P24

DX- DX+

SD

2.3.5 AF-300 G11 Drive Cable Size, Tightening Torque and Circuit Protection Rating

Incoming Device

Tightening Torque lb-Inch (Nm)

Cable size AWG

Input Fuse

HP

L1/R, L2/S,

L3/T

(Nominal)

L1/R, L2/S,

L3/T

(Maximum) (*1)

Auxiliary

Input

R0, T0

Input

Circuit

Breaker

(*1)

L1/R, L2/S,
L3/T, UVW,

P1, P(+), DB,

N(-)

E(G)

R0, T0

Control

L1/R, L2/S,

L3/T

U, V, W

P1, P(+), N(-),

DB

R0,

T0

Control

230VAC Input

0.25

3

3

3

15

10.6 (1.2)

-

6.2 (0.7)

-

22

0.5

5

6

3

15

-

16

-

1

10

15

3

20

-

-

2

15

20

3

30

20.8 (2.36)

10.6 (1.2)

14

3

20

30

3

40

14

5

35

50

3

60

10

7.5

60

80

3

100

31.0 (3.5)

8

10

70

125

3

125

6

15

100

150

3

175

51.3 (5.8)

4

20

125

200

3

225

3

25

150

225

3

250

2

30

175

250

3

300

1

40

200

-

5

200

119(13.5)

4/0

1/0

2/0

10

50

225

-

5

225

239(27)

119(13.5)

Qty2 - 1

3/0

4/0

60

300

-

5

300

Qty2 - 2/0

4/0

Qty2 - 1

75

350

-

5

350

Qty2 - 3/0

Qty2 - 1/0

Qty2 - 2/0

100

300

-

5

300

425(48)

239(27)

Qty 2 - 2/0

Qty2 - 3/0

Qty2 - 4/0

125

400

-

5

400

Qty2 - 4/0

Qty2 - 4/0

Qty2 - 250

460VAC Input

0.5

3

3

3

15

10.6 (1.2)

-

6.2 (0.7)

-

22

1

5

6

3

15

-

16

-

2

10

10

3

15

20.8 (2.36)

10.6 (1.2)

14

3

15

15

3

20

5

20

25

3

35

14

7.5

30

45

3

50

31.0 (3.5)

12

10

40

60

3

70

10

15

50

90

3

90

51.3 (5.8)

20

70

110

3

110

8

25

80

125

3

150

6

30

100

125

3

175

4

40

100

-

10

100

119(13.5)

2

3

3

10

50

125

-

10

125

1

2

2

60

175

-

10

175

2/0

2

1

75

150

-

10

150

3/0

1/0

2/0

100

175

-

10

175

239(27)

119(13.5)

2/0

3/0

4/0

125

200

-

10

200

239(27)

3/0

4/0

Qty2 - 1

150

225

-

10

225

Qty2 - 1/0

Qty2 - 1/0

Qty2 - 1/0

200

300

-

10

300

425(48)

Qty2 - 1/0

Qty2 - 2/0

Qty2 - 3/0

250

400

-

10

400

Qty2 - 3/0

Qty2 - 3/0

Qty2 - 4/0

300

450

-

10

450

Qty2 - 4/0

Qty2 - 250

Qty2 - 300

350

500

-

10

500

Qty2 - 250

Qty2 - 300

Qty2 - 350

400

600

-

10

600

Qty2 - 350

Qty2 - 400

Qty2 - 500

450

700

-

10

700

Qty2 - 500

Qty2 - 500

Qty2 - 700

500

700

-

10

700

Qty2 - 600

Qty2 - 600

Qty2 - 800

600

1000

-

10

1000

Qty2 - 700

Qty2 - 750

Qty2 - 1000

(*1)Class J Fuse or Circuit Breaker reted 600V with the maximum current rating as shown in the above table shall be connected to the drive for 30HP and less.
Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Wire size from NEC tables 310-16. Copper wire rated 60 Deg. C for 100amps or less, 75 Deg. C for over 100 amps in 30 Deg. C ambient and 1.25 times Drive rated amps.
These are minimum wire sizes : consult and confirm to local and national codes.