2) control circuit terminals – GE Industrial Solutions AF-300 G11 User Manual
Page 33
2-16
Data subject to change without notice 7/07. © 2007 GE Drives
(2) Control circuit terminals
30A
Y5A CMY
Y3
Y1
C1
FMA FMP PLC
X1
X2
X3
X4
X5
X6
X7
X8
X9
30C
30B Y5C
Y4
Y2
11
12
13
V2
CM
CM FWD REV P24
P24
DX- DX+
SD
2.3.5 AF-300 G11 Drive Cable Size, Tightening Torque and Circuit Protection Rating
Incoming Device
Tightening Torque lb-Inch (Nm)
Cable size AWG
Input Fuse
HP
L1/R, L2/S,
L3/T
(Nominal)
L1/R, L2/S,
L3/T
(Maximum) (*1)
Auxiliary
Input
R0, T0
Input
Circuit
Breaker
(*1)
L1/R, L2/S,
L3/T, UVW,
P1, P(+), DB,
N(-)
E(G)
R0, T0
Control
L1/R, L2/S,
L3/T
U, V, W
P1, P(+), N(-),
DB
R0,
T0
Control
230VAC Input
0.25
3
3
3
15
10.6 (1.2)
-
6.2 (0.7)
-
22
0.5
5
6
3
15
-
16
-
1
10
15
3
20
-
-
2
15
20
3
30
20.8 (2.36)
10.6 (1.2)
14
3
20
30
3
40
14
5
35
50
3
60
10
7.5
60
80
3
100
31.0 (3.5)
8
10
70
125
3
125
6
15
100
150
3
175
51.3 (5.8)
4
20
125
200
3
225
3
25
150
225
3
250
2
30
175
250
3
300
1
40
200
-
5
200
119(13.5)
4/0
1/0
2/0
10
50
225
-
5
225
239(27)
119(13.5)
Qty2 - 1
3/0
4/0
60
300
-
5
300
Qty2 - 2/0
4/0
Qty2 - 1
75
350
-
5
350
Qty2 - 3/0
Qty2 - 1/0
Qty2 - 2/0
100
300
-
5
300
425(48)
239(27)
Qty 2 - 2/0
Qty2 - 3/0
Qty2 - 4/0
125
400
-
5
400
Qty2 - 4/0
Qty2 - 4/0
Qty2 - 250
460VAC Input
0.5
3
3
3
15
10.6 (1.2)
-
6.2 (0.7)
-
22
1
5
6
3
15
-
16
-
2
10
10
3
15
20.8 (2.36)
10.6 (1.2)
14
3
15
15
3
20
5
20
25
3
35
14
7.5
30
45
3
50
31.0 (3.5)
12
10
40
60
3
70
10
15
50
90
3
90
51.3 (5.8)
20
70
110
3
110
8
25
80
125
3
150
6
30
100
125
3
175
4
40
100
-
10
100
119(13.5)
2
3
3
10
50
125
-
10
125
1
2
2
60
175
-
10
175
2/0
2
1
75
150
-
10
150
3/0
1/0
2/0
100
175
-
10
175
239(27)
119(13.5)
2/0
3/0
4/0
125
200
-
10
200
239(27)
3/0
4/0
Qty2 - 1
150
225
-
10
225
Qty2 - 1/0
Qty2 - 1/0
Qty2 - 1/0
200
300
-
10
300
425(48)
Qty2 - 1/0
Qty2 - 2/0
Qty2 - 3/0
250
400
-
10
400
Qty2 - 3/0
Qty2 - 3/0
Qty2 - 4/0
300
450
-
10
450
Qty2 - 4/0
Qty2 - 250
Qty2 - 300
350
500
-
10
500
Qty2 - 250
Qty2 - 300
Qty2 - 350
400
600
-
10
600
Qty2 - 350
Qty2 - 400
Qty2 - 500
450
700
-
10
700
Qty2 - 500
Qty2 - 500
Qty2 - 700
500
700
-
10
700
Qty2 - 600
Qty2 - 600
Qty2 - 800
600
1000
-
10
1000
Qty2 - 700
Qty2 - 750
Qty2 - 1000
(*1)Class J Fuse or Circuit Breaker reted 600V with the maximum current rating as shown in the above table shall be connected to the drive for 30HP and less.
Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Wire size from NEC tables 310-16. Copper wire rated 60 Deg. C for 100amps or less, 75 Deg. C for over 100 amps in 30 Deg. C ambient and 1.25 times Drive rated amps.
These are minimum wire sizes : consult and confirm to local and national codes.