12.5 Drive Function Code Access

All of the drive function codes are accessible through the RS485 serial interface. Drive function codes are mapped to
RTU holding registers. A drive function code RTU address is 2 bytes in length. The high byte corresponds to a code that
represents the drive parameter sort (F–M). The low byte corresponds to the drive parameter number within the sort (0 -
99).

Code

Sort

Name

Code

Sort

Name

0

F

Basic function

5

A

Motor 2 function

1

E

Terminal function

6

o

Option function

2

C

Control function

7

S

Command/function data

3

P

Motor 1 function

8

M

Monitor data

4

H

High level function

For example, drive function code M11, output current, is addressed as RTU parameter number 080B hexadecimal or
2059 decimal.

12.6 Command and Monitor Data Registers

The command and monitor function codes are used to control the operation of the drive and monitor the status variables
through the serial interface. The command and monitor function codes are not accessible from the drive keypad
interface. Drive parameter H30 and digital input signal LE must be enabled to operate the drive from the Modbus
interface. If LE is not assigned to a digital input (X1-X9), the signal will default to ON.

Frequency Setting Registers

Read/

Data

Address Code

Name

Unit

Variable Range

Min. unit

Write

Format

1793

S01

Frequency command

-

-20000–20000
(max. frequency at ± 20000)

1

R/W

2

1797

S05

Frequency command

Hz

0.00–400.00

0.01

R/W

5

Note:
1) If both S01 and S05 are set, the drive will ignore the setting of S05.
2) A data setting that exceeds the setting range is possible, but the actual action will be limited by the drive configura-
tion.
Operation command data Registers

Address Code

Name

Unit

Variable Range

Min. unit

Read/

Data

Write

Format

1798

S06

Operation command

-

Refer to the data format [14]

-

R/W

14

1799

S07

Universal Do

-

Refer to the data format [15]

-

R/W

15

1804

S12

Universal Ao

-

-20000–20000

1

R/W

2

(100% output at ± 20000 )

Note:
1) Since X1–X9 are configurable input commands, it is necessary to set the functions by E01–E09.
2) The alarm reset is executed, when RST signal changes from ON to OFF even if there are no alarms.
3) Universal Do is a function that utilizes the drive’s digital outputs via communication.

Function data Registers

Address Code

Name

Unit

Variable range

Min. unit

Read/

Data

Write

Format

1800

S08

Acceleration time F07

s

0.1–3600.0

0.1

R/W

3

1801

S09

Deceleration time F08

s

0.1–3600.0

0.1

R/W

3

1802

S10

Torque limit level 1
(driving) F40

%

-20.00 –200.00, 999

1

R/W

5

1803

S11

Torque limit level 2
(braking) F41

%

0.00, 20.00–200.00, 999

1

R/W

5

Note:
1)

The writing of data out of range is treated as out of range error.

2)

Use a value of 7FFF

H

to enter 999 for torque limit functions.

high byte

low byte

drive parameter sort code

drive parameter number