6 dc link reactor, Terminal – GE Industrial Solutions AF-300 G11 User Manual

Page 34

Advertising
background image

2-17

Data subject to change without notice 7/07. © 2007 GE Drives

2.3.6 DC Link Reactor

Dimensions in inches

Terminal

Width

Depth

Height

Note:

• AF-300 G11 Drives rated 100 Hp and above are furnished with a DC link reactor. This reactor must be installed

between terminal P1 and P+ prior to commissioning of the Drive.

• The weight of the DC Link Reactor is not included with that of the Drive.

• DC Link Reactor is provided as open type and is separately mounted. Enclosure to be provided by others.

Hp

Model No.

Width

Depth

Height

Weight

Loss [W]

230V G11

100

DCR2-75B

7.87

10.63

7.09

37

55

125

DCR2-90B

7.09

11.02

8.46

37

57

460V G11

100

DCR4-75B

7.48

10.63

6.89

35

58

125

DCR4-90B

7.48

11.02

7.87

44

64

150

DCR4-110B

7.48

11.02

7.87

46

73

200

DCR4-132B

7.87

11.02

8.07

55

84

250

DCR4-160B

8.27

12.6

8.07

68

90

300

DCR4-200B

8.27

12.99

9.06

75

126

350

DCR4-220B

8.66

13.78

9.06

81

131

400

DCR4-280B

8.66

14.57

9.65

95

133

450

DCR4-315B

9.84

12.01

8.78

88

150

500

DCR4-355B

9.84

12.99

8.78

99

205

600

DCR4-400B

9.84

13.78

9.17

106

215

Advertising