P:motor parameters, H:high performance functions – GE Industrial Solutions AF-300 G11 User Manual

Page 56

Advertising
background image

5-3

Data subject to change without notice 7/07. © 2007 GE Drives

Func.

Factory Setting

Data

Change

No.

Setting Range

Unit

Min.

30 HP

40 HP

Format

during op

C20

JOG frequency

C20

JOG Hz

0.00 to 400.00 Hz

Hz

0.01

5.00

5

Y

C21

PATTERN

(mode select)

C21

PATTERN

0,1,2

-

-

0

1

operation

C22

(Stage 1)

C22

STAGE 1

Operation time: 0.00 to 6000 s

s

0.01

0.00 F1

13

C23

(Stage 2)

C23

STAGE 2

F1 to F4 and R1 to R4

0.00 F1

13

C24

(Stage 3)

C24

STAGE 3

0.00 F1

13

C25

(Stage 4)

C25

STAGE 4

0.00 F1

13

C26

(Stage 5)

C26

STAGE 5

0.00 F1

13

C27

(Stage 6)

C27

STAGE 6

0.00 F1

13

C28

(Stage 7)

C28

STAGE 7

0.00 F1

13

C30

Frequency command 2

C30

FREQ CMD 2

0 to 11

-

-

2

1

N

C31

Offset adjust

(terminal [12])

C31

BIAS 12

-100.0 to +100.0%

%

0.1

0.0

4

Y

C32

(terminal [C1])

C32

GAIN 12

0.0 to +200.0%

%

0.1

100.0

3

Y

5-31

C33

Analog setting signal filter

C33

REF FILTER

0.00 to 5.00s

s

0.01

0.05

5

Y

P:Motor Parameters

P01

Number of motor 1 poles

P01

M1 POLES

2 to 14

-

2

4

9

N

P02

Motor 1

(capacity)

P02

M1-CAP

Up to 30 HP: 0.01 to 60 HP

Hp

0.01

motor capacity

5

40 HP and above: 0.01 to 600 HP

P03

(rated current)

P03

M1-Ir

0.00 to 2000 A

A

0.01

motor rated current

19

N

P04

(tuning)

P04

M1 TUN1

0, 1, 2

-

-

0

21

N

P05

(on-line tuning)

P05

M1 TUN2

0, 1

-

-

0

1

N

P06

(no-load current)

P06

M1-Io

0.00 to 2000 A

A

0.01

standard rated value

19

N

P07

(%R1 setting)

P07

M1-%R1

0.00 to 50.00%

%

0.01

standard rated value

5

Y

P08

(%X setting)

P08

M1-%X

0.00 to 50.00%

%

0.01

standard rated value

5

Y

P09

Slip compensation control

P09

SLIP COMP1

0.00 to 15.00 Hz

Hz

0.01

0.00

5

Y

H:High Performance Functions

H03

Data initializing

H03

DATA INIT

0, 1

-

-

0

1

N

H04

Auto-reset

(times)

H04

AUTO-RESET

0, 1 to 10 times

-

1

0

1

Y

H05

(reset interval)

H05

RESET INT

2 to 20 s

s

1

5

1

Y

H06

Fan stop operation

H06

FAN STOP

0, 1

-

-

0

1

Y

H07

ACC/DEC pattern (mode select)

H07

ACC PTN

0,1,2,3

-

-

0

1

N

H08

Rev. phase sequence lock

H08

REV LOCK

0, 1

-

-

0

1

N

H09

Start mode

H09

START MODE

0, 1, 2

-

--

0

1

N

H10

Energy-saving operation

H10

ENERGY SAV

0, 1

-

-

0

1

Y

H11

DEC mode

H11

DEC MODE

0, 1

-

-

0

1

Y

H12

Instantaneous OC limiting

H12

INST CL

0, 1

-

-

1

1

N

H13

Auto-restart

(restart time)

H13

RESTART t

0.1 to 10.0 s

s

0.1

0.1

0.5

3

N

H14

(freq. fall rate)

H14

FALL RATE

0.00 to 100.00 Hz/s

Hz/s

0.01

10.00

5

H15

(holding DC voltage)

H15

HOLD V

3-phase, 230V class: 200 to 300V

V

1

200V class: 235V

1

3-phase, 460V class: 400 to 600V

400V class: 470V

H16

(OPR command self hold time)

H16

SELFHOLD t

0.0 to 30.0 s, 999

s

0.1

999

3

H18

Torque control

H18

TRQ CTRL

0, 1, 2

-

-

0

1

H19

Active drive

H19

AUT RED

0, 1

-

-

0

1

Y

H20

PID control

(mode select)

H20

PID MODE

0, 1, 2

--

-

0

1

N

5-38

H21

(feedback signal)

H21

FB SIGNAL

0, 1, 2, 3

-

-

1

1

N

H22

(P-gain)

H22

P-GAIN

0.01 to 10.00 times

-

0.01

0.1

5

Y

H23

(I-gain)

H23

I-GAIN

0.0, 0.1 to 3600 s

s

0.1

0.0

3

Y

H24

(D-gain)

H24

D-GAIN

0.00 s , 0.01 to 10.0 s

s

0.01

0.00

5

Y

H25

(feedback filter)

H25

FB FILTER

0.0 to 60.0 s

s

0.1

0.5

3

Y

H26

PTC thermistor

(mode select)

H26

PTC MODE

0, 1

0

1

Y

H27

(level)

H27

PTC LEVEL

0.00 to 5.00V

V

0.01

1.60

5

Y

H28

Droop operation

H28

DROOP

9.9 to 0.0 Hz

Hz

0.1

0.0

4

Y

H30

Serial link

(function select)

H30

LINK FUNC

0, 1, 2, 3

-

-

0

1

Y

H31

Modbus-RTU

(address)

H31

ADDRESS

0 (broadcast), 1 to 247

-

1

1

1

N

H32

(mode select on no response error)

H32

MODE ON ER

0, 1, 2, 3

-

-

0

1

Y

H33

(timer)

H33

TIMER

0.0 to 60.0 s

s

-

2.0

3

Y

H34

(baud rate)

H34

BAUD RATE

0, 1, 2, 3

-

-

1

1

Y

H35

(data length)

H35

LENGTH

0 (8-bit fixed)

-

-

0

1

Y

H36

(parity check)

H36

PARITY

0, 1, 2

-

-

0

1

Y

H37

(stop bits)

H37

STOP BITS

0 (2-bit), 1(1-bit)

-

-

0

1

Y

H38

(no response error detection time)

H38

NO RES t

0 (no detection), 1 to 60 s

s

1

0

1

Y

H39

(response interval)

H39

INTERVAL

0.00 to 1.00 s

s

0.01

0.01

5

Y

5-42

5-43

5-37

5-39/40

5-41

5-36

Pg.

5-29

5-29/30

5-30

5-32

5-33

5-34

5-35

Y

N

Y

Name

LCD Display

N

N