GE Industrial Solutions AF-300 G11 User Manual

Page 82

Advertising
background image

5-29

Data subject to change without notice 7/07. © 2007 GE Drives

C20 Jog frequency

C 2 0

J O G

H z

Setting range: 0.00 to 400.00 Hz

This function sets a frequency for the motor jogging
operation, which is different from the normal operation.

The jogging frequency is used for operation when the
jogging mode signal is received from the keypad panel or
control terminal. For details, see the explanations of
E01 Terminal X1 to E09 Terminal X9.

C21 Pattern operation (operation selection)

C 2 1

P A T T E R N

Pattern operation is an automatic operation according to
a preset operation time, direction of rotation, accelera-
tion and deceleration time, and frequency.

When using this function, set F01 Frequency setting to

10 (pattern operation).

[Related Functions: F01, C30 = 10]

The following operation patterns can be selected.

Value

Operation Pattern

0

Perform a pattern operation cycle, then stop
operation.

1

Perform pattern operation repeatedly.
Operation is stopped by the STOP operation.

2

Perform a pattern operation cycle, then
continue operation at the last set frequency.

C22-C28 Pattern operation (stage 1 to 7)

C 2 2

S T A G E

1

C 2 3

S T A G E

2

C 2 4

S T A G E

3

C 2 5

S T A G E

4

C 2 6

S T A G E

5

C 2 7

S T A G E

6

C 2 8

S T A G E

7

Seven stages are operated in order of function codes,
according to the values set in C22 Pattern operation
(stage 1) to C28 Pattern operation (stage 7). Each
function sets the operation time and the direction of
rotation for each stage and assigns values to acceleration
and deceleration time.

Set or assign item

Value range

Operation time

0. 00 to 6000s

Rotation

F: Forward (counterclockwise)

direction

R: Reverse (clockwise)

Acceleration and

1: Acceleration time 1 (F07)

deceleration time

Deceleration time 1 (F08)
2: Acceleration time 2 (E10)
Deceleration time 2 (E11)
3: Acceleration time 3 (E12)
Deceleration time 3 (E13)
4: Acceleration time 4 (E14)
Deceleration time 4 (E15)

Note: The operation time is represented by the three
most significant digits, hence, can be set with
only three high-order digits.

Set the operation time to 0.00 for any unused stages,
which are skipped during operation.

In regard to the set frequency value, the multi-step
frequency function is assigned according to the table
below. Seven frequencies can be set for C05 Multi-step
frequency 1 to C11 Multi-step frequency 7.

Stage No.

Operation Frequency

Stage 1

Multi-step frequency 1 (C05)

Stage 2

Multi-step frequency 2 (C06)

Stage 3

Multi-step frequency 3 (C07)

Stage 4

Multi-step frequency 4 (C08)

Stage 5

Multi-step frequency 5 (C09)

Stage 6

Multi-step frequency 6 (C10)

Stage 7

Multi-step frequency 7 (C11)

Setting example

100 F 3

Acceleration and deceleration
time (code): 3

Motor rotating direction:
Forward (counterclockwise)

Operation time: 100s

Advertising